Instruction manual
21
33 I: Integral time (s) 00.0 – 100 10.0 *1
34 D: Differential time (s) 0.00 – 10.0 0.00 *1
35 PID OFFSET
000: Positive direction
001: Negative direction
000 *1
36 PID OFFSET adjust (%) 000 – 109 000 *1
37 PID Update time (s) 00.0 - 02.5 00.0 *1
38
PID Sleep mode
threshold
00.0~200Hz 00.0
39 PID Sleep delay time 00.0~25.5 00.0
40
Frequency Up/ Down
control using MFIT
000: UP/Down command is available.
Set frequency is held when inverter
stops.
001: UP/Down command is available.
Set frequency resets to 0Hz when
inverter stops.
002: UP/Down command is available.
Set frequency is held when inverter
stops. Up/Down is available in stop.
000
41
Local/Remote frequency
control select
(Run command by the
Run/Stop key)
000: UP/Down key on keypad sets
frequency
001: Potentiometer on the keypad set
frequency
000
42
Terminal S5 function
(option)
007
43
Terminal S6 function
(option)
000: Forward
001: Reverse
002: Preset Speed Command 1
003: Preset Speed Command 2
004: Preset Speed Command 3
005: Jog Frequency Command
006: Emergency Stop(E.S.)
007: Base Block (b.b.)
008: Select 2
nd
accel/decel time.
009: Reset
010: Up Command
011: Down Command
012: Control signal switch
013: Communication control signal
switch
014: Acceleration/ deceleration disable
015:
Master/auxiliary speed source select
016: PID function disable
017: Analog frequency signal input(
terminal AIN)
018: PID feedback signal (terminal AIN)
019: DC Brake signal
009
44
Multi-function input
terminal S1~S6 signal
scan time (mSec ×8)
001~100 010
45
Confirming AIN signal
scan time (mSec x 8 )
001~100 050