Instruction manual
20
11 Acceleration time 2 00.1~999 Sec 05.0
*1 *2
12 Deceleration time 2 00.1~999 Sec 05.0
*1 *2
13 Fan control
000: Auto-run at set temperature
001: Run when inverter runs
002: Always run
003: Always stop
001
This function
only available
for IP20 type,
For IP65
type , fan will
run while
power is on.
14 Control mode
000:Vector control
001:V/F Control
000 *4
15 V/F Pattern setting 001 ~ 007 001/004
16
V/F base output voltage
set
198~265V / 380~530V 220/440
17
Max output frequency
(Hz)
00.2 – 200 50.0/60.0
18
Output voltage ratio at
max frequency (%)
00.0 – 100 100
19 Mid frequency(Hz) 00.1 – 200 25.0/30.0
20
Output voltage ratio at
mid frequency (%)
00.0 – 100 50.0
21
Min output frequency
(Hz)
00.1 – 200 00.5/00.6
22
Output voltage ratio at
Min frequency (%)
00.0 – 100 01.0
23
Torque Boost Gain
(V/F)
00.0 ~ 30.0% 00.0 *1
24
Slip Compensation Gain
(V/F)
00.0 ~100% 00.0
*1
25 Motor no load current
Varies with
motor rating *4
26
Electronic thermal relay
protection for motor
(OL1)
000: Enable motor protection
001: Disable motor protection
000
27 Skip frequency 1(Hz) 00.0~200 00.0 *1
28
Skip frequency 2(Hz) 00.0~200 00.0 *1
29
Skip frequency range
(±Hz)
00.0~30.0 00.0 *1
30 PID operation mode
000: PID Function unavailable
001: PID control, Bias D control
002: PID Control, Feedback D control
003: PID Control, Bias D reverse
characteristics control.
004: PID Control, Feedback D reverse
characteristics control.
000
31 PID Error gain 0.00 – 10.0 1.00 *1
32 P: Proportional gain 0.00 – 10.0 01.0 *1