Technical Literature

6
AIRFLOW SELECTION FOR VARIABLE SPEED MODELS
B6VM
A-cabinet
Cooling Airflow Heating Airflow
A/B Switch Setting
0=OFF,1=ON
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
0=OFF,1=ON
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
0 0 0 0 0 525 0 0 600
0 0 0 0 1 560 0 5 800
0 0 0 1 0 600 0 8 1000
0 0 0 1 1 625 0 10 1000
0 0 1 0 0 700 0 15 1300
0 0 1 0 1 750 0 20 n/a
0 0 1 1 0 800 0 25 n/a
0 0 1 1 1 850
0 30 n/a
0 1 0 0 0 875
0 1 0 0 1 890
0 1 0 1 0 930
0 1 0 1 1 950
0 1 1 0 0 1000
0 1 1 0 1 1050
0 1 1 1 0 1125
0 1 1 1 1 1200
B6VM
B-cabinet
Cooling Airflow Heating Airflow
A/B Switch Setting
0=OFF,1=ON
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
0=OFF,1=ON
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
1 0 0 0 0 525 1 0 700
1 0 0 0 1 560 1 5 900
1 0 0 1 0 600 1 8 1100
1 0 0 1 1 650 1 10 1100
1 0 1 0 0 700 1 15 1300
1 0 1 0 1 750 1 20 1500
1 0 1 1 0 800 1 25 n/a
1 0 1 1 1 850
1 30 n/a
1 1 0 0 0 875
1 1 0 0 1 950
1 1 0 1 0 1050
1 1 0 1 1 1150
1 1 1 0 0 1250
1 1 1 0 1 1350
1 1 1 1 0 1400
1 1 1 1 1 1600
B6VM
C-cabinet
Cooling Airflow Heating Airflow
A/B Switch Setting
(*=either0or1)
COOL Switch Setting
0=OFF,1=ON
Airflow
(CFM)
A/B Switch Setting
(*=either0or1)
Heater Kit
Installed (KW)
Airflow
(CFM)
5 6 7 8
* 0 0 0 0 1100 * 0 800
* 0 0 0 1 1200 * 5 1000
* 0 0 1 0 1250 * 8 1200
* 0 0 1 1 1300 * 10 1200
* 0 1 0 0 1350 * 15 1400
* 0 1 0 1 1400 * 20 1600
* 0 1 1 0 1450 * 25 1800
* 0 1 1 1 1500
* 30 2000
* 1 0 0 0 1550
* 1 0 0 1 1600
* 1 0 1 0 1650
* 1 0 1 1 1700
* 1 1 0
0 1750
* 1 1 0 1 1800
* 1 1 1 0 1900
* 1 1 1 1 2000
NOTES:
• Airowvalueslistedarefor240Voperation.For
208Voperation,multiplyA&Bcabinetvaluesby.95;
forC-cabinetvaluesmultiplyby.90
• Whenmatchedwithtwo-stageoutdoorunitstheairow
onlow(Y1orW1)inputonlywillbe70%ofthevalues
showninthistable.