Technical Literature
4
PHYSICAL SPECIFICATIONS
P5RF Models
(a) Amperage and wire size based on refrigeration system only. See Electrical Data tables for supplemental
electric heaters. Refer to National Electric Code for additional derating factors for field installed conductors.
(b) Use time delay fuse or "HACR" type circuit breaker.
Model No. P5RF-KA X24KA X36KA X48KA X60KA
System Cooling Capacities
Cooling Btuh 24,000 35,400 47,500 57,500
SEER 15 15 15 15
EER 12 12 12 12
Electric Rating - 60Hz (a)
Operating Voltage Range 187 - 253 187 - 253 187 - 253 187 - 253
Min. Circuit Ampacity (a) 18.1 26.1 37.7 40.1
Field Wire Size - AWG (a) 12 10 8 8
Delay Fuse - Max. (b) 25 40 50 60
Total Unit - Amps FLA 15.5 21.9 32.4 34.3
Compressor Data
Volts 208 - 230 208 - 230 208 - 230 208 - 230
Rated Load Amps 11.7 15.3 21.2 28.8
Lock Rotor Amps 58 83 106 152
Fan Motor and Condenser
2 Speeds 2 Speeds
Fan Motor - HP - RPM 1/5 - 1100 1/4 - 1100 1/2 - 1100 1/2 - 1100
Fan Motor - Amps 1.2 1.2 5.3 5.3
Fan Diameter / CFM 20” - 2800 20” - 2800 20” - 3400 24” - 4000
Motor and Evaporator
Blower Motor - HP - ECM 1/2 1/2 3/4 3/4
Blower Motor - Amps 3.8 3.8 5.4 5.4
CFM @ E.S.P. - in. W.C. 800 @ .30 1000 @ .30 1500 @ .30 1700 @ .30
Refrigerant Charge R-410A - Oz. 128 131 171 240
Shipping weight - lbs. 299 303 380 416
Sound Rating 73 75 75 77
MODEL IDENTIFICATION CODE
H 3 HK 008 - H 0 1
Heater
Heater Kit
3-Pkgd. Units
Electric
Heater KW
No. of Breakers
Electric Code
H=240-1-60
Stages
Sequencer