Technical Literature



      


Cooling Btu/h 23800 28600 36000 40500 47000 56000
SEER 13 13 13 13 13 13
EER 10.8 10.6 11 11 11 10.8
Sound Ratings 73 73 76 76 78 78

Volts-Cycles-Phase (1)
208/230-
60-1
208/230-
60-1
208/230-
60-1
208/230-
60-1
208/230-
60-1
208/230-
60-1
Operating Voltage Range 187 - 253 187 - 253 187 - 253 187 - 253 187 - 253 187 - 253
Total Amps 14.4 14.9 19.9 26.9 31.2 37.9
Delay Fuse - Max. (2) 25 25 35 50 60 70
Min. Circuit Ampacity 16.8 17.4 23.7 31.9 37.3 45.3

Outdoor Coil
Face Area (SQ/FT) 8.95 8.95 12.54 12.54 12.54 14.1
Type MC-23 MC-23 MC-23 MC-23 MC-23 MC-21
PSC
Fan Motor
Fan Motor - Amps 1 1 1.1 1.5 1.5 1.5
RPM 825 825 1100 1100 1100 1100
HP 1/5 1/5 1/8 1/4 1/4 1/4
Fan Blade
Dia - # Blades 20-3 20-3 20-3 20-3 20-3 20-3
SCFM 2800 2800 2800 3000 3000 3000
Compressor
Data
RLA 9.6 10.1 15 20 24.3 29.4
LRA 60.5 60 88 112 117 134

Indoor Coil
Face Area (SQ/FT) 3.6 3.6 5.1 5.1 5.1 5.8
Type MC-20 MC-20 MC-20 MC-20 MC-20 MC-20
Metering Device
Fixed
Orifice
Fixed
Orifice
Fixed
Orifice
Fixed
Orifice
Fixed
Orifice
Fixed
Orifice
ECM Blower
Amps 3.8 3.8 3.8 5.4 5.4 7
RPM 1050 1050 1050 1050 1050 1050
HP 1/2 1/2 1/2 3/4 3/4 1
CFM @ ESP, WC 755 @ .30 925 @ .30 1190 @ .30 1500 @ .30 1535 @ .30 1820 @ .30

Oz. 58 57 66 62 57 69

Shipping 244 249 280 297 301 317
(1) Operating Voltage Range: 187v min. - 253v max. Amperage and wire size based on refrgieration system only. See electrical data tables for
supplemental electric heaters.
(2) HACR Type Circuit Breakers may be used.
(3) Airflow performance is with a dry coil.