User`s guide
3-2
Getting Started
Model No.
Input
Feeds
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
VMR Series
VMR-4HS15-1 1 ea, 15 Amp 100 to 120 VAC 12 Amps 12 Amps* 12 Amps*
VMR-4HS15-2 1 ea, 15 Amp 100 to 240 VAC 10 Amps 12 Amps* 12 Amps*
VMR-8HS20-1 1 ea, 20 Amp 100 to 120 VAC 15 Amps 16 Amps* 16 Amps*
VMR-8HS20-2 1 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 16 Amps*
VMR-8HS16-3 1 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 16 Amps
VMR-8HD20-1 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 32 Amps*
VMR-8HD20-2 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps*
VMR-8HD16-3 2 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 32 Amps
VMR-16HD20-1 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps * 32 Amps*
VMR-16HD20-2 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
VMR-16HD16-3 2 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 32 Amps
VMR-HD4D16 2 ea, 16 Amp 200 to 240 VAC 16 Amps 16 Amps 32 Amps
VMR-HD4D20 2 ea, 20 Amp 100 to 240 VAC 16 Amps 16 Amps* 32 Amps*
VMR-HD4D30 2 ea, 30 Amp 200 to 240 VAC 16 Amps 24 Amps* 48 Amps*
VMR-HD4D30-12B 2 ea, 30 Amp 200 to 240 VAC 16 Amps 24 Amps 48 Amps*
VMR-HD4D32 2 ea, 32 Amp 200 to 240 VAC 16 Amps 32 Amps 64 Amps
VMR-HD4D32-12B 2 ea, 32 Amp 200 to 240 VAC 16 Amps 32 Amps 64 Amp
NPSSeries
NPS-8HS20-1 1 ea, 20 Amp 100 to 120 VAC 15 Amps 16 Amps* 16 Amps*
NPS-8HS20-2 1 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 16 Amps*
NPS-8HS16-3 1 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 16 Amps
NPS-8HD20-1 2 ea, 20 Amp 100 to 120 VAC 15 Amps 16 Amps* 32 Amps*
NPS-8HD20-2 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
NPS-8HD16-3 2 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 32 Amps
NPS-8H20-ATS-1 2 ea, 20 Amp** 100 to 120 VAC 15 Amps 16 Amps* 16 Amps*
NPS-8H20-ATS-2 2 ea, 20 Amp** 100 to 240 VAC 10 Amps 16 Amps* 16 Amps*
NPS-16HD20-1 2 ea, 20 Amp 100 to 120 VAC 15 Amps 16 Amps* 32 Amps*
NPS-16HD20-2 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
NPS-16HD16-3 2 ea, 16 Amp 200 to 240 VAC 10 Amps 16 Amps 32 Amps
* In accordance with UL requirements, this value has been de-rated to 80%.
** NPS-ATS series units feature dual, redundant power inlets.
3.1.2. Connect your PC to the VMR or NPS
The VMR or NPS unit can either be controlled by a local PC, that communicates with the
unit via the SetUp port, controlled via external modem, or controlled via TCP/IP network.
In order to switch plugs or select parameters, commands are issued to the VMR or NPS
via either the Network Port or SetUp Port. Note that it is not necessary to connect to
both the Network and SetUp Ports, and that the SetUp Port can be connected to either a
local PC or External Modem.
• NetworkPort: Connect your 10Base-T or 100Base-T network interface to the VMR
or NPS Network port.
• SetupPort: Use the DX9F-WTI Adapter supplied with the unit to connect your PC
COM port to the VMR or NPS SetUp Port.
• ExternalModem: Use the optional DX9M-RJ-KIT (not included) to connect your
external modem to the VMR or NPS Setup (RS232) Port.