User`s guide
Apx-2
Appendices
A.2. RSM-8R Series Units
PowerInput/Output:
Voltage: 100 - 120 VAC, 50/60 Hz or 208 - 240 VAC, 50/60 Hz
ACInputFeed:
RSM-8R4andRSM-8R4-DCMUnits: 15 Amps Max. Input Feed
RSM-8R8Units: 20 Amps Max. Input Feed per Inlet
ACInlets:
RSM-8R4andRSM-8R4-DCMUnits: One (1) IEC320-C14
RSM-8R8Units: Two (2) IEC320-C20
ACOutlets:
RSM-8R4-1andRSM-8R4-1-DCM: 4 each, NEMA 5-15R Outlets
RSM-8R4-2andRSM-8R4-2-DCM: 4 each, IEC320-C13 Outlets
RSM-8R8-1: 8 each, NEMA 5-15R Outlets
RSM-8R8-2: 8 each, IEC320-C13 Outlets
RS232PortInterface:
Connectors: Eight (8) RJ45 connectors (DTE pinout.)
Coding: 7/8 bits, Even, Odd, No Parity, 1, 2 Stop Bits.
FlowControl: XON/XOFF, RTS/CTS, Both, or None.
DataRate: 300 to 115.2K bps (all standard rates).
InternalModem: V.34
Physical/Environmental:
Dimensions-RSM-8R4-1andRSM-8R4-2:
Width: 19” (48.3 cm) (Including Rack Brackets)
Depth: 6.5” (16.5 cm)
Height: 1.75” (4.5 cm) One Rack U
Dimensions-RSM-8R8-1andRSM-8R8-2:
Width: 19” (48.3 cm) (Including Rack Brackets)
Depth: 8.75” (22.2 cm)
Height: 1.75” (4.5 cm) One Rack U
Dimensions-RSM-8R4-1-DCMandRSM-8R4-2-DCM:
Width: 9” (22.9 cm)
Depth: 5” (12.7 cm)
Height: 3.5” (8.9 cm)
OperatingTemperature: 32˚F to 122˚F (0˚C to 50˚C)
Humidity: 10 - 90% RH
AgencyApprovals: FCC, UL, CE (240 VAC Units)
Venting: Side vents are used to dissipate heat generated within the unit. When mounting the
unit in an equipment rack, make certain to allow adequate clearance for venting.
ControlPorts:
EthernetPort: 100Base-T
InternalModemPort(PhoneLine): RJ11 connector for connection to your telco line