Alarm Configuration
Subject: This parameter is used to define the text that will appear in the "Subject"
field for all email notification messages generated by this alarm.
(Default = "Alarm: Power Cycle")
AlarmInputParameters: Provides access to a submenu that is used to Enable/
Disable the alarm at each Alarm Input, name Alarm Inputs, set trigger levels for
each Alarm Input and also select load shedding parameters for each Alarm Input.
Notes:
The Alarm Input Alarm must be enabled in order to access the Alarm Input
Parameters submenu.
Text Interface: When accessing the Alarm Input Parameters submenu via
the Text Interface, first type 11 and press [Enter] to access the first Alarm
Input Parameters submenu. From the Alarm Input Parameters submenu, key
in the number of the desired Alarm Input and then press [Enter] to display
the Alarm Input Parameters submenu for an individual Alarm Input.
Web Browser Interface: To access the Alarm Input Parameters submenu
via the Web Browser Interface, click the Alarm Input Parameters button at the
bottom of the Alarm Input configuration menu. In the Web Browser Interface,
all Alarm Input Parameters for all four Alarm Inputs may be defined via a
single submenu.
The Alarm Input Parameters submenu will allow you to define the following
parameters for each Alarm Input:
Name: Can be used to define a unique name for each Alarm Input.
(Default = undefined.)
Enable: Enables/Disables each Alarm Input. (Default = Off)
Level: Defines the trigger level for each Alarm Input as either Open or Closed.
For example, if the Level is set to "Open" and the Alarm Input Alarm is properly
configured, an alarm will be generated when the dry contact relay connected to
the corresponding Alarm Input is Opened. (Default = Open)
LoadShedding: Allow the Alarm Input Alarm to automatically shut off user
specified circuits or circuit groups when an Alarm is generated. This feature
works identically to the Load Shedding feature in the Over Temperature Alarms.
For more information, please refer to Section 7.1.1. (Default = undefined)