User`s guide
15-2
Saving and Restoring Configuration Parameters
15.1.2. Sending RPC Parameters to a File - Web Browser Interface
The Web Browser Interface also includes a download function that can be used to save
RPC parameters to an XML format file on your PC or laptop. To save parameters via the
Web Browser Interface, proceed as follows:
Note: Although RPC parameters can be saved to a file via either the Text
Interface or Web Browser Interface, saved parameters can only be restored via
the Text Interface. The Restore Parameters function is not available via the Web
Browser Interface.
1. Click on the "Download Unit Configuration" button on the left hand side of the Web
Browser Interface screen.
2. After a brief pause, your browser may display a prompt asking if you want to open
or save the downloaded file. At this point, you can either select the "Save" option to
save the parameters file to the download folder on your PC, or select "Save As" to
pick a different location and/or filename for the saved parameters file.
15.2. Restoring Saved Parameters
This section describes the procedure for using your terminal emulation program to send
saved parameters to the RPC.
Note: The Restore Parameters feature is only available via the Text Interface.
1. Start your terminal emulation program and access the RPC’s Text Interface
command mode using an account that permits Administrator level commands.
2. Configure your terminal emulation program to upload an ASCII text file.
3. Upload the ASCII text file with the saved RPC parameters. If necessary, key in the
file name and directory path.
4. Your terminal emulation program will send the ASCII text file to the RPC. When the
terminal program is finished with the upload, make certain to terminate the Upload
mode.
Note: If the RPC detects an error in the file, it will respond with the "Invalid
Parameter" message. If an error message is received, carefully check the
contents of the parameters file, correct the problem, and then repeat the Upload
procedure.
5. If the parameter upload is successful, the RPC will send a confirmation message,
and then return to the command prompt. Type /S and press [Enter], the Status
Screen will be displayed. Check the Status Screen to make certain the unit has
been configured with the saved parameters.