User`s guide

Table Of Contents
3-3
Getting Started
1. AccessCommandMode: The VMR/NPS includes two user interfaces; the Text
Interface and the Web Browser Interface. The Text Interface is available via Local
PC, SNMP, SSH Client, Telnet, or Modem, and the Web Browser interface is only
available via TCP/IP network. In addition, when contacted via PDA, the VMR/NPS
will also present a third interface, which is similar to the Web Browser Interface, but
offers limited command functions.
a) ViaLocalPC: Start your communications program and then press [Enter].
b) ViaSSHClient: Start your SSH client, enter the default IP address
(192.168.168.168) for the VMR/NPS and invoke the connect command.
c) ViaWebBrowser: Make certain that Web Browser access is enabled as
described in the Section 5.9 in this User's Guide. Start your JavaScript enabled
Web Browser, enter the default VMR/NPS IP address (192.168.168.168) in the
Web Browser address bar, and then press [Enter].
d) ViaTelnet: Make certain that Telnet access is enabled as described in
Section 5.9. Start your Telnet client, and enter the VMR/NPS default IP address
(192.168.168.168).
e) ViaModem: Make certain the VMR/NPS SetUp Port is configured for Modem
Mode as described in Section 5.8, then use your communications program to
dial the number for the external Modem connected to the SetUp Port.
2. Username/PasswordPrompt: A message will be displayed, which prompts you
to enter your username and password. The default username is “super” (all lower
case, no quotes), and the default password is also “super”. If a valid username
and password are entered, the VMR or NPS will display either the Main Menu (Web
Browser Interface) or the Port Status Screen (SSH, Telnet, or Modem.)
3. TestSwitchingFunctions: You may wish to perform the following tests in order to
make certain that the VMR or NPS is responding to commands. When switching
and reboot commands are executed, the VMR/NPS Output Status LEDs will also
turn On or Off to indicate the status of each outlet.
a) RebootOutlet:
i. WebBrowserInterface: Click on the "Plug Control" link on the left hand
side of the screen to display the Plug Control Menu. From the Plug
Control Menu, click the down arrow in the row for Plug A1 to display the
dropdown menu, then select "Reboot" from the drop down menu and click
on the "Execute Plug Actions" button.
ii. TextInterface: Type /BOOT A1 and press [Enter].
b) SwitchOutletOff:
i. WebBrowserInterface: From the Plug Control Menu, click the down
arrow in the "Action" column for Plug A1 to display the drop down menu,
then select "Off" from the drop down menu and click on the "Execute Plug
Actions" button.