User`s guide
Table Of Contents
- Figure 2.1: VMR Series - Front Panel (Model VMR-16HD20-1 Shown)
- Figure 2.2: VMR Series - Back Panel (Model VMR-16HD20-1 Shown)
- Figure 2.3: NPS Series - Front Panel (Model NPS-16HD20-1 Shown)
- Figure 2.4: NPS Series - Back Panel (Model NPS-16HD20-1 Shown)
- Figure 5.1: Boot Priority Example 1
- Figure 5.2: Boot Priority Example 2
- Figure 9.1: The Help Menu (Administrator Mode; Text Interface - VMR Shown)
- Figure 14.1: Web Access Parameters (Text Interface Only)
- Figure B.1: RS232 SetUp Port Interface
- 1. Introduction
- 2. Unit Description
- 3. Getting Started
- 4. Hardware Installation
- 5. Basic Configuration
- 5.1. Communicating with the VMR or NPS Unit
- 5.2. Configuration Menus
- 5.3. Defining System Parameters
- 5.4. User Accounts
- 5.5. Managing User Accounts
- 5.6. The Plug Group Directory
- 5.7. Defining Plug Parameters
- 5.8. Serial Port Configuration
- 5.9. Network Configuration
- 5.10. Save User Selected Parameters
- 6. Reboot Options
- 7. Alarm Configuration
- 8. The Status Screens
- 9. Operation
- 10. SSH Encryption
- 11. Syslog Messages
- 12. SNMP Traps
- 13. Operation via SNMP
- 14. Setting Up SSL Encryption
- 15. Saving and Restoring Configuration Parameters
- 16. Upgrading VMR/NPS Firmware
- 17. Command Reference Guide
- Appendix A. Specifications
- Appendix B. Interface Descriptions
- Appendix C. Customer Service
- Index

17-6
Command Reference Guide
/ON Switch Plug(s) ON
Switches selected plugs(s) or Plug Group(s) On, as described in Section 9.2.2. When
the /ON command is used to switch more than one plug, Boot/Sequence Delay Period
will be applied as described in Section 5.7.
Note: When this command is invoked in Administrator Mode or SuperUser
Mode, it can be applied to all VMR/NPS plugs and Plug Groups. When this
command is invoked in User Mode, it can only be applied to the plugs and/or
Plug Groups that have been enabled for the account.
Availability: Administrator, SuperUser, User
Format: /ON <s>[,Y] [Enter]
Where:
s The number or name of the plug(s) or Plug Group(s) that you intend to
Switch On. To apply the command to several plugs, enter a plus sign (+)
between each plug number. To apply the command to a range of plugs,
enter the numbers for the first and last plugs in the range, separated by a
colon character (:). To apply the command to all plugs allowed by your
account, enter an asterisk character (*).
,Y (Optional) Suppresses the command confirmation prompt.
Example:
Assume that your account allows access to Plug A2 and Plug A3. To switch Plugs A2
and A3 On, without displaying the optional command confirmation prompt, invoke
following command line:
/ON A2+A3,Y [Enter]