User`s manual
Western Reserve Controls WRC-CANR-DF-DN User’s Manual
PUB 14.1 Series 3
8
Table 4-4 Diagnostic Status LEDs (labeled DNG)
LED State Module Status Meaning
OFF Normal Normal operation.
Green Fiber Link OK Serial link to fiber network operating.
Red Time-out
Unit has not received a serial message from
the fiber link.
Flashing Red Communications error
Internal FIFO stack has overflowed on the
fiber link interface.
The Green TXF and RXF LED’s are illuminated when data is actively transmitted out to the fiber link.
4.3. DIP Switch Settings
The WRC-CANR-DF has an 8-pole DIP switch.
• Switch positions 1-4 are used to set the baud rate of the CANR on which it is located
(the local unit).
• Switch positions 5-8 are used to set the baud rate on the CANR at the other end of the
fiber cable (the Remote Device).
The baud rates can be set independently, or one side can take its baud rate from the other side (in
the “Remote” setting).
Table 4-5 Baud Rate Settings for Switches
Local Position
1
Position 2
Position 3
Position 4
Baud rate
Remote Position
5
Position
6
Position
7
Position 8
Meaning
125K
CLOSED CLOSED CLOSED CLOSED Fixed
250K
CLOSED CLOSED CLOSED OPEN Fixed
500K
CLOSED CLOSED OPEN CLOSED Fixed
Autobaud
CLOSED CLOSED OPEN OPEN Autobaud
Remote
OPEN OPEN OPEN OPEN
Takes baud rate from the
opposite end device.
If both sides are remote,
Autobaud from either
side.
N/A ALL OTHER POSITIONS Reserved for future use