7 Troubleshooting
This section identifies some of the common problem observed when commissioning or operating
a DeviceNet and JDM.
Problem
:
JDM powers up, then the module status LED turns Red. JDM does not communicate over
the network.
Possible Solutions:
1. JDM has detected a duplicate MacID (DeviceNet address). Change the JDM’s MacID
to an unused address and cycle power.
Problem
:
Module Status LED is solid Green
Network Status LED is flashing Green
Device will not communicate on the network
Possible Solutions:
1. Network does not have a terminating resistor. Add a 121 ohm resistor across the
CAN_H and CAN_L signals at the first and last nodes.
Problem
:
Module Status LED is solid Red
Network Status LED is flashing Green or solid Green
Device will not perform serial I/O – does not return a poll response and ignores future
commands.
Possible Solutions:
1. JDM received an unintelligible response from the Modbus device and the time-out is
set to 0. Set the time-out value to a non-zero number greater than the longest
message time expected from the Modbus device.
Problem
:
JDM does not receive a response from the Modbus slave.
Possible Solutions:
1. The ASCII-RTU mode selection is not correct.
2. The serial link baud rate does not match the Modbus device baud rate.
3. The communication parameters are not correct, including parity and number of data
bits.
4. The Modbus address is not correct in the I/O command.
5. The Modbus device may not support the Modbus specific commands being issued.