User`s manual
Western Reserve Controls 1782-JDM User’s Manual
PUB 24.0
18
Phoenix Contact MSTBA 2.5/5-G-5.08/AU or equivalent
DeviceNet Cable: 5-contact plug (female contacts)
Phoenix Contact MSTB 2.5/5-ST-5.08/AU or equivalent (included)
Status Indicators:
Module Status: green/red bi-color LED
Network Status: green/red bi-color LED
Network Termination:
External terminating resistor (optional per user system configuration)
Serial port:
Baud rate
: 300, 600, 1200, 2400, 4800, 9600, 19.2k, 39.4k baud
(software selectable)
Parity
: Odd, even or none (software selectable)
Data bits
: 7 or 8 (software selectable)
Cable Connection:
JDM: 3-pin pluggable header (male)
Phoenix Contact MSTBA 2.5/3-G-5.08/AU or equivalent
Serial Cable: 3-contact plug (female contacts)
Phoenix Contact MSTB 2.5/3-ST-5.08/AU or equivalent (included)
Status Indicators
:
Transmit Active: green LED
Receive Active: green LED
Voltage Isolation
: Optional 500V isolated RS232 version
Maximum power
: 200 mA @ 11 Vdc - 90 mA @ 25V dc unregulated power supply, not
including Output loads (power provided by the DeviceNet network, or
Auxiliary 24VDC power)
Mounting
: DIN rail mount, EN50022
Size
: Depth: 3.54” (90 mm)
Width: 0.98” (25 mm)
Height: 3.11” (79 mm)
Operating Temp
: 0-60 ºC
Humidity
: 0-95% RH, non-condensing
Agency Approvals:
UL listed (pending), CE (pending)