User`s manual

Western Reserve Controls WRC-CANR-DF-DN User’s Manual
PUB 14.1
7
Green LED TXF is illuminated when data is actively transmitted out to the fiber link.
Green LED RXF is on solid when its fiber cable is connected to the TX port of an active CANR-DF.
This LED flashes when data is actively received from the fiber link.
4.3. DIP Switch Settings
The WRC-CANX-XX Multiplexer has a 6-pole DIP switch. Switch positions 5 and 6 are used to set
the baud rate. (Switch positions 1-4 are reserved for future functions.)
Table 4-4 Baud Rate Settings
Baud rate Position
1-4
Position 5 Position 6
125K n/a ON ON
250K n/a ON OFF
500K n/a OFF ON
Autobaud n/a OFF OFF
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
0 1 0 1
0 1
0 1
Figure 4-2 DIP Switch Setting for Baud Rate
4.4. Power Requirements
The WRC-CANR-DF-DN CAN-Bus Extender subsystem is powered from the 11-25 Vdc provided by
the DeviceNet network. The WRC-CANR-DF-DN consumes 70 mA of current at 24 Vdc, or 1.8 Watts,
typical. See Section 3.
4.5. Network Cabling and Configuration