4. Recalculate the network traffic and bandwidth without the CANX.
10. Summary of Changes to Series 3 from Rev 2
To facilitate implementation of the new Series 3 CANX products for customers that are currently
users of the CANX Revision 2.xx products, this section summarizes the product changes from Rev 2 to
Series 3.
10.1. DIP Switch Baud Rate Settings
Several new options exist for setting the baud rate on the CANX Series 3.
The Series 3 has an 8-position DIP switch block. All 8 switches are defined and used.
Both sides’ baud rates can be set up independently.
A “remote mode” exists which allows either side to set its baud rate based on the other
side’s BR in either fixed baud or autobaud.
See Section 5.2 above for details.
10.2. Indicator LED’s
The definition of some states of the LEDs have changed. Refer to Table 5-2, Table 5-3 and Table 5-4
for details.
10.3. Terminating Resistors
The Series 3 has an on-board terminating resistor on each CAN connection that can be selectively
included or excluded from the network circuit. With jumpers W1 and/or W2 in place, the CANX puts a 121-
ohm resistor across the CAN_H and CAN_L lines on sub-network sides A and/or B. See Figure 5-1and
Figure 5-2 for the location of these jumpers.
10.4. Field Programmable Updates
The CANX Series 3 has its program held in flash memory, which can be updated in the field.
Contact the factory for details.