User`s manual
Western Reserve Controls WRC-CANX-xx Series 3
PUB 14.0 User’s Manual
9
Figure 5-2 WRC-CANX-NEM Series 3 Dimensional Drawing
5.2. DIP Switch Settings
The WRC-CANX-XX has an 8-pole DIP switch.
• Switch positions 1-4 are used to set the Network A baud rate.
• Switch positions 5-8 are used to set the Network B baud rate.
The baud rates can be set independently, or one side can take its baud rate from the other side (in
the “Remote” setting).
Table 5-1 Baud Rate Settings for Switches
Side
A
Position
1
Position 2
Position 3
Position 4
Baud rate
Side
B
Position
5
Position
6
Position
7
Position 8
Meaning
125K
CLOSED CLOSED CLOSED CLOSED Fixed
250K
CLOSED CLOSED CLOSED OPEN Fixed
500K
CLOSED CLOSED OPEN CLOSED Fixed
Autobaud
CLOSED CLOSED OPEN OPEN Autobaud
Remote
OPEN OPEN OPEN OPEN
Takes baud rate from
opposite side setting.
If both sides are remote,
Autobaud from either
side.
N/A
Reserved for future use
--NET A- --NET B--
1 2 3 4 5 6 7 8
OPEN
NSA
NSB
DGN
MS
NETWORK A
5.11” (130 mm)
2.27” ( 57,7 mm)
SW1
NETWORK B
DeviceNet
Male, Mini
DeviceNet
Female,
Mini
W1
W2