User`s manual
Western Reserve Controls WRC-CANR-DF-DN User’s Manual
PUB 14.1
7
Green LED TXF is illuminated when data is actively transmitted out to the fiber link.
Green LED RXF is on solid when its fiber cable is connected to the TX port of an active CANR-DF.
This LED flashes when data is actively received from the fiber link.
4.3. DIP Switch Settings
The WRC-CANX-XX Multiplexer has a 6-pole DIP switch. Switch positions 5 and 6 are used to set
the baud rate. (Switch positions 1-4 are reserved for future functions.)
4.3.1. Slide Swith version
Table 4-4 Baud Rate Settings – SLIDE Switch Only
Baud rate Position
1-4
Position 5 Position 6
125K n/a ON ON
250K n/a ON OFF
500K n/a OFF ON
Autobaud n/a OFF OFF
125k baud 250k baud
500k baud Autobaud
Figure 4-2 DIP Switch Settings – SLIDE Switch Only