User`s manual
Western Reserve Controls, Inc. 1782-JDC User’s Manual
11
all of the consecutive bytes up to and including the delimiter after the transmit record
number has changed. If the length is non-zero, the JDC will send up to the number of
bytes specified by the length without regard to the transmit delimiter and ignoring
any “junk” characters after the specified amount of bytes. The format is:
Table 2-4 DeviceNet Consume Assembly / Transmit Data String
BYTE MEANING
Byte 1 Record Counter
Byte 2 String Length (number of data bytes)
Byte 3 ASCII Character 1
Byte 4 ASCII Character 2
….
Byte 21 ASCII Character 19
….
Byte 126 ASCII Character 124
3. Begin scanning the JDC. Enter data that you want to send on the serial link. On receipt of
a change to the record number, the JDC will transmit the data. If any data is in the
receive buffer, the received data will be returned as a poll response. (If the sequence
number is the same as the previous response, the JDC will not re-send the string.)
NOTE: If using the Byte-Swap Mode (Parameter 10 set to enabled) all strings being sent must
have the length set. Using a zero length will prevent the byte swapping from occurring.