1 Overview
The 1782-JDM is a family of DeviceNet-to-ModBus interfaces that allows you to easily connect and
integrate a ModBus-capable device into a DeviceNet system.
The ModBus device’s real-time data is read and written as I/O by the DeviceNet Master via Polled I/O. The
devices set up parameters, if any, can be read and written with the Explicit Messaging technique. The
1782-JDM will operate with any compliant DeviceNet master software system or other device.
The JDM is defined as a Communications Adapter device on the DeviceNet system. It has a 3-pin plug
connector for RS232/485 or a 5-pin connector for RS422 to cable to the ModBus interface port on the
MODBUS DEVICE and a 5-pin pluggable DeviceNet connector for connections to the DeviceNet network.
The device performs the DeviceNet baud rate selection automatically when it is powered up on a network.
The JDM has one assigned DeviceNet address that is set by a 6-position DIP switch on the unit. Other
parameters are software-configurable and are changed from their default values by third-party DeviceNet
configuration tools. Each JDM has 2 standard green/red DeviceNet LED’s for module status and network
status and two green LED’s to indicate RS232/485/422 transmit and receive activity.
All the ModBus device parameters are accessible for read or write over DeviceNet via the JDM, which
allows the user the option of using DeviceNet tools and software to define or monitor these parameters in
addition to other off-the-shelf or custom software utility using the ModBus port connection.
KEY
0=RIGHT
TOGGLE
ARM
1=LEFT
1782-JDM
DeviceNet Converter
V+
CAN_H
CAN-L
V-
RX/SG-
TX/SG+
GND
ADDR
= 0
N/C
Figure 1-1 1782-JDM