3.5 DeviceNet Network Configuration
DeviceNet specifications provide for a maximum network distances for the main trunk line and
drop lines, depending upon the baud rate used on the network. They are:
Table 3-5 Network Maximum Lengths
Trunk Line Length Drop Length
Maximum Distance Maximum Cumulative
Baud Rate Meters Feet Meters Feet Meters Feet
125k baud 5OO m 164O ft 6 m 2O ft 156 m 512 ft.
25Ok baud 25O m 82O ft 6 m 2O ft 78 m 256 ft.
5OOk baud 1OO m 328 ft 6 m 2O ft 39 m 128 ft.