2. Switch setting changes do NOT take effect until the device is reset with either a device RESET
command (to the class 1 Identity object) or a power cycle.
2.2 How to Change the DeviceNet Baud Rate
1. The baud rate defaults to autobaud. You can change the baud rate in software to a fixed baud rate
using your configuration tool or an explicit message to Set Class 3 (DeviceNet Class), Instance 1,
Attribute 2 to 1 (125k), 2 (250k), or 3 (500k), from the Master.
2. If you change the baud rate, the new baud rate will not become effective until the unit is power cycled
or a Reset command is issued to the JDM from the Master.
2.3 How to Install the ModBus Device Network
1. The communication between the ModBus device(s) and the 1782-JDM is an RS-232 3-wire full-duplex
link , an RS-485 network, using a 2-wire half-duplex differential signal between the devices, or an RS-
422 5-wire full-duplex link.
2. Connect an appropriate cable to your ModBus device. See your ModBus device users manual for
details.
3. Connect the other end of the cable to the JDM using the 3-point or 5-point terminal plug provided. See
Table 2.2 and 2.3 below.
4. Turn on power to the ModBus device.
Table 2-2 RS-232/485 Connector Signals
Pin # RS232
Signal
RS485
Signal
Designator
1 Receive Signal - RX/SIG-
2 Transmit Signal + TX/SIG+
3 Ground Ground GND
Table 2-3 RS-422 Connector Signals
Pin # Designator
RS422
Signal
5 TX- Transmit -
4 TX+ Transmit +
3 GND Ground
2 RX- Receive -
1 RX+ Receive +