Application Designed to safely transfer low viscosity petroleum fuels such as gasoline (up to 15% alcohol blends
such as E15), diesel fuel (up to 20% biodiesel blends such as B20) and kerosene. Pump is designed for
permanent mounting on vented storage tanks.
Pump Housing Cast Iron
Performance:
Pump Rate Up to 25 GPM (94 LPM) Up to 25 GPM (94 LPM)
Duty Cycle 30 min. ON, 30 min. OFF 30 min. ON, 30 min. OFF
Suction Lift: Up to 15 feet (4.6 meters) Up to 15 feet (4.6 meters)
Discharge Lift: Up to 10 feet (3 meters) Up to 10 feet (3 meters)
Operating Temperature -20°F to +125°F (-29°C to +52°C)
Bypass Pressure 20 PSI
Electrical Specications:
Input 12-volt DC 24-volt DC
Current Draw 35 amps 20 amps
Motor 2000 RPM, 4/10 hp (300 watts) 2000 RPM, 4/10 hp (300 watts)
Motor Approval cULus Listed. Class I, Division 2, Group D cULus Listed. Class I, Division 2, Group D
Motor Protection 40 amp circuit breaker 20 amp circuit breaker
Cord* 18 feet of 10 gauge (5.4 meters) 18 feet of 10 gauge (5.4 meters)
Fuse 40 amp 20 amp
Mechanical Connection:
Bung 2 inch NPT 2 inch NPT
Inlet 1 inch NPT 1 inch NPT
Outlet 1 inch NPT 1 inch NPT
Accessories:
Hose Type Buna-N Electrically Conductive Discharge Hose Buna-N Electrically Conductive Discharge Hose
Hose Size 1 NPT x 12 ft. (3.7 m) 1 NPT x 12 ft. (3.7 m)
Manual Nozzle 1 inch Leaded 1 inch Leaded
Automatic Nozzle 1 inch Diesel 1 inch Diesel
Weight:
M-3X25-AD 61.2 lbs/27.8 kg 59.3 lbs/26.9 kg
M-3X25-ML 57.2 lbs/26.0 kg 57.5 lbs/26.1 kg
M-3X25CX-AD 69.3 lbs/31.5 kg 69.3 lbs/31.5 kg
M-3025CB-ML 65.6 lbs/29.8 kg --
* Weight Centering Inlet Base models include 18 feet of 10 gauge (5.4 meters)
SPECIFICATIONS