User guide

9
6641-2201
Interface specifications
Power and fault relay port PWR
Rated voltage 24 to 110 VDC
Operating voltage 24 to 110 VDC ±40%
Rated current 40 mA @ 110 VDC
140 mA @ 24 VDC
Rated frequency DC
Inrush current, I
2
t Max 0.02 A
2
s @ 24 – 110 VDC
Startup current * 7 Apeak @ 24 110 VDC
Polarity Reverse polarity protected
Redundant power input No
Isolation to Connections X1 X8 and to ground, 1500 VAC.
Fault relay belongs to the same isolation group as the power
supply lines (fault relay signals are also contained within
PWR).
Connection 4 pin male M12 connector with A-code
Connector size M12, recommended cable area 0.5 mm
2
recommended
(minimum 0.25 mm
2
), cable dimensions depend on choice of
M12 connector
Shielded cable Not required, twisted pair is recommended
Fault relay resistance < 10
Operating voltage Up to 110 VDC
Max continuous current 250 mA
* If external power supply is used it must meet specified startup current.
M12 A-Coded
Power
Connector
Position Direction Description
1 U+ Positive supply voltage
2 Out Alarm relay (status) +
3 0 V Negative supply voltage
4 Out Alarm relay (status)
Housing Shield Chassis of product (ground)