User guide

27
6614-2202
…  TR-36 – Secure Call-back
The TR-36 is connected to a PLC which one want to restrict access to.The TR-36 can 
support access control through the Secure Callback function.In this example password 
and callback to a predefined number is chosen.The modem in the calling end is here 
chosen to be a PSTN modem,but can be any of the PSTN, ISDN or GSM modem from 
Westermo product range.
The DTE serial speed between the PLC – TR-36 and TDW-33 – PC is assumed to be 
9600 8N1 but can be chosen to fit the actual system requirement.
Configure the TR-36
AT&F Set the unit to factory default
AT+IPR=9600 DTE baudrate 9600
AT+ICF=3,4 Character framing 8 data,1 stop,parity 
none
ATS0=1 Auto answer after first ring
ATQ1E0&C1&K0&A1 Suitable for PLC communication
AT&W Save settings
AT*WCB=4 Callback enabled,Password in one or more 
positions in *wcbpwdx (x= 1,2 or 3), call-
back to number in wcbtab 
(*wcbpwd1 corresponds to *wcbtab1.. .)
AT*WCBTAB=1,”+4670428000”,”n3Y9kA6otYZu8” Define callback number and password 
in position 1.
When the password  is entered number 
+4670428000 will be called.
AT*WCBTIME=10 Define delay time between hangup  
an callback.
The TR-36 will wait 10 s after hangup to 
callback to allow the analogue modem to 
hangup.
Configure the TDW-33
AT&F Set the unit to factory default
AT+IPR=9600 DTE baudrate 9600
AT+ICF=3,4 Character framing 8 data,1 stop,parity 
none
ATS0=1 Auto answer after first ring
AT&W Store default settings