6651-2221 ODW-720-F1 Fibre Optic Modem Industrial Converter RS-232 to Fibre Optic Link. Point to Point applications www.westermo.
Legal information The contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, are made in relation to the accuracy and reliability or contents of this document. Westermo reserves the right to revise this document or withdraw it at any time without prior notice.
Safety ! Before installation: Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this unit. This unit should only be installed by qualified personnel. This unit should be built-in to an apparatus cabinet, or similar, where access is restricted to service personnel only.
Note. Fibre Optic Handling Fibre optic equipment requires careful handling as the fibre components are very sensitive to dust and dirt. If the fibre is disconnected from the modem, the protective plug on the transmitter/receiver must be replaced. The protective plug must be kept on during transportation. The fibre optic cable must also be protected in the same way. If this recommendation is not followed, it can jeopardise the warranty.
ATEX Information (Applicable for ODW-720-F1 EX only) General This unit is intended for use in Zone 2 hazardous location only. Marking II 3 G Ex nA IIC T4 Gc SPECIAL CONDITION WARNING – DO NOT SEPARATE WHEN ENERGIZED Indicate that this unit complies with relevant European standards that are harmonised with the 94/9/EC Directive (ATEX). II 3 G Ex nA IIC T4 Gc SPECIAL CONDITION 6651-2221 Equipment group II.
Ratings Power Ambient temperature Ingress protection (IP) Maximum surface temperatur (12 – 48) VDC; 300 mA –40ºC ≤ Ta ≤ +70ºC IP21 135ºC (temperature class T4) Safety Control Drawing Degree of protection Ambient temperature Installation spacing IP 21 –40°C to +70°C Minimum 25 mm above / below Minimum 10 mm left / right Direction relative this unit! Position 1 2 3 FP Descripton In & out / Relay contact (NO) In & out / Relay contact (C) In & out / Relay contact (NC) Input / Output values Uin = 60 VDC m
SPECIAL CONDITION FOR SAFE USE Ambient temperature: This unit is designed for use in extreme ambient temperature conditions as follows: –40 ºC ≤ Ta ≤ +70 ºC Installation in an apparatus cabinet: This unit requires installation in an Ex certified apparatus cabinet suitable for the area of use and providing a degree of protection of at least IP54. Resistance to impact: This unit requires installation in an apparatus cabinet where adequate resistance to impact is provided by the apparatus cabinet.
Declaration of Conformity Westermo Teleindustri AB Declaration of conformity The manufacturer Westermo Teleindustri AB SE-640 40 Stora Sundby, Sweden Herewith declares that the product(s) Type of product Model Art no Industrial fiberoptic repeaters/media converters ODW-700 series 3651-07xx ODW-700EX series 3651-37xx is in conformity with the following EC directive(s).
Type tests and environmental conditions Electromagnetic Compatibility Phenomena Test ESD EN 61000-4-2 RF field AM modulated IEC 61000-4-3 RF field 900 MHz Fast transient ENV 50204 EN 61000-4-4 Surge EN 61000-4-5 RF conducted EN 61000-4-6 Pulse Magnetic field Voltage dips and interruption EN 61000-4-9 EN 61000-4-11 Mains freq. 50 Hz Mains freq.
Functional description Switches LED’s POWER +VA +VB COM O V P Internal Electronics COM STATUS ODW-720 O V P NO C NC RS -232 DCD RD TD SG DSR RTS CTS SHIELD CH 1 OVP Over Voltage Protection OCP Over Current Protection SFP Fibre transceiver TX RX Converter serial interface – optical fibre ODW-720-F1 is a fibre optic modem that converts between electrical RS-232 and a fibre optic link. ODW-720-F1 can also be used to convert from RS-232 to RS-485 by using one ODW720-F1 and one ODW-730-F1.
Interface specifications Power Rated voltage Operating voltage Rated current Rated frequency Inrush current I²t Startup current* Polarity Redundant power input Isolation to Connection Connector size Shielded cable ODW-720-F1: 12 to 48 VDC and 24 VAC ODW-720-F1 Ex: 12 to 48 VDC ODW-720-F1: 10 to 60 VDC and 20 to 30 VAC ODW-720-F1 Ex: 10 to 60 VDC 300 mA @ 12 V 150 mA @ 24 V 75 mA @ 48 V ODW-720-F1: DC and 48 to 62 Hz ODW-720-F1 Ex: DC 0.2 A²s 1.
RS-232 Electrical specification Data rate Protocol Data format Data retiming Transmission range Isolation to Connection Shielded cable Conductive housing EIA RS-232 300 bit/s – 250 kbit/s Asynchronous or synchronous 9 – 12 bits in asynchronous mode Any type in synchronous mode Asynchronous mode only 15 m Status and Power port 9-pin D-sub female (DCE) Not required, except when installed in railway applications as signalling and telecommunications apparatus and located close to rails* Isolated to all other
FX (Fibre) Fibre connector Fibre type Wavelength nm, connector 1 Wavelength nm, connector 2 Transmitter Output optical power min/max Receiver Input sensitivity, max Receiver Input optical power, max Optical power budget, worst-case Bit error rate (BER) Transceiver type Laser class 6651-2221 Bi-Di LC-40 LC Simplex Singlemode 9/125 μm Tx 1310, Rx 1550 Tx 1550, Rx 1310 –8/0 dBm Bi-Di LC-20 LC Simplex Singlemode 9/125 μm Tx1310, Rx 1550 Tx 1550, Rx 1310 –14/8 dBm –34 dBm –32 dBm –3 dBm 0 dBm 26 dB 18 d
Location of Interface ports, LED’s and DIP-switches ODW-720-F1 DIP-switches accessible under lid (for details see page 16) LED Indicators (for details see page 15) Status screw terminal Position 1 2 3 FX(Fibre) (for details see page 12–13) Description Contact with C when fibre optical links are in operation Common Open (no contact with C) when fibre optical links are not in operation Product marking NO C NC Power screw terminal Position Direction* 1 In 2 3 4 In In In Description Common voltage Vo
LED indicators LED Status Description PWR ON Power is on. OFF Power is off. Power FP Not used CH 2 Not used CH 1 Channel 1 link status TD RD FL R Failure link remote FL L Failure link local ON Fiber link to other unit has been established at CH 1. Flashing Optical power detected but link to other unit has not been established at CH 1. OFF No optical power detected and no link to other unit has been established at CH 1.
! DIP-switch settings Before DIP-switch settings: Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap) Note: Disconnect power before DIP-switch settings. S1 S2 The ODW-720-F1 DIP-switches are pre-set from the factory, so that the unit can be used for point-to-point applications, togheter with an additional ODW-720-F1, straight out of the box, without the need for any type of user configuration.
Start up guide, point-to-point application Follow the steps below to get the unit up and running in a simple application. Master POWER COM +VA +VB COM Slave CH 1 TX RX POWER COM +VA +VB COM CH 1 TX RX …… Using the factory DIP-switch settings: …… Set DIP-switch S2:1 as desired. …… Connect The fibre link between the ODW-720-F1. …… Connect the power supply to both ODW-720-F1. …… After a few seconds the fibre link should be in operation, indicated by an active CH1 LED.
About the interfaces Power The power terminal has two independent inputs, +VA and +VB, allowing redundant power input. The ODW-720-F1 power supply is galvanically isolated from all other interfaces. Optical fibre interfaces ODW-720-F1 uses Small Form Factor Pluggable (SFP) transceivers. This means that a wide range of different fibre transceivers and connectors can be used (see page 12–13). RS-232 interface The RS-232 interface is a female 9-position D-sub.
Mounting This unit should be mounted on 35 mm DIN-rail, which is horizontally mounted inside an apparatus cabinet, or similar. Snap on mounting, see figure. CLICK! CLICK! Cooling This unit uses convection cooling. To avoid obstructing the airflow around the unit, use the following spacing rules. Minimum spacing 25 mm (1.0 inch) above /below and 10 mm (0.4 inches) left /right the unit. Spacing is recommended for the use of unit in full operating temperature range and service life. 10 mm * (0.
Westermo • SE-640 40 Stora Sundby, Sweden Tel +46 16 42 80 00 Fax +46 16 42 80 01 E-mail: info@westermo.com www.westermo.com Sales Units Westermo Data Communications China sales.cn@westermo.com www.cn.westermo.com France infos@westermo.fr www.westermo.fr Germany info@westermo.de www.westermo.de North America info@westermo.com www.westermo.com Singapore sales@westermo.com.sg www.westermo.com Sweden info.sverige@westermo.se www.westermo.se United Kingdom sales@westermo.co.uk www.westermo.co.