User guide

8
6622-2231 29000448
Type tests and environmental conditions
Phenomena Test Description Test levels
ESD EN 61000-4-2 Enclosure contact  ± 4 kV
Enclosure air ± 8 kV
RF eld AM modulated  EN 61000-4-3 Enclosure 3 V/m 80% AM (1 kHz), 80 – 1 000 MHz,  1 
400 MHz – 2 000
Fast transient EN 61000-4-4 Signal ports ± 0.5 kV
Power ports ± 1 kV
Surge EN 61000-4-5 Telecom/Signal ports  ± 0.5 kV line to earth
Power ports ± 2 kV line to earth, ± 2 kV line to line
RF conducted EN 61000-4-6 Power ports 3V/m 80% AM (1 kHz), 0.15 – 80 MHz
Voltage dips and  
interruption 
EN 61000-4-11 AC power ports 10 & 100 ms, interruption 
10 ms, 30% reduction 
100 ms, 60% reduction 
5000 ms, >95% reduction 
+30% above & –20% below rated voltage
Radiated emission  EN 55022 Enclosure Class B
FCC part 15 Class B
Conducted emission EN 55022 AC power ports Class A
FCC part 15 AC power ports Class B
EN 55022 DC power ports Class B
Temperature Operating 
DR-260
–20 to +70º Celsius   
–4 to +158º Fahrenheit
Operating 
DR-260 + 3G
–20 to +55º Celsius   
–4 to +131º Fahrenheit
Storage & Transport –40 to +85º Celsius   
–40 to +185º Fahrenheit
Humidity Operating 5 to 95% relative humidity
Storage & Transport 5 to 95% relative humidity
Altitude Operating 2000 m / 70 kPa
Reliability prediction 
(MTBF)
Bellcore  
RQGR at 40°C
131 400 hours 
Enclosure Pressed steel
Dimension W x H x D DR-260 239 x 40 x 151 mm 
9.4 x 1.6 x 5.9 inches
DR-260 + 3G 239 x 40 x 159 mm 
9.4 x 1.6 x 6.2 inches
Weight 0.9 kg
Degree of protection IEC529 Enclosure IP 40
Cooling Convection
Mounting Horizontal on 35 mm DIN-rail or flat on 
level surface