Operator`s manual
Load
4-Pole Frequency
Generator
Voltage
Applied
Speed (rpm) (Hertz) 120V (110)
240V (220)
Plants Plants
None 1830
62
122
240
(1530) (52) (112)
(224)
Half
1800 60
120
240
(1500)
(50) (110)
(220)
Full 1755
59
110
220
(1455) (49) (100) (200)
The output voltage should
be
checked periodically
to
ensure proper operation of the generating plant and
the appliances it supplies.
If an
AC
voltmeter or ampmeter
is
not installed to monitor voltage and load, check it with a portable
meter and amp-probe.
Preventive Maintenance (Generator)
Maintenance
on
the
generator
is
minimal.
1.
Keep the generator clean, dry and well-ventilated.
2.
Ensure that all connections are clean and tight and that cables carrying
AC
voltage are properly
supported and protected against chafing.
3.
The rear armature bearing
is
lubricated and sealed; therefore,
no
maintenance
is
required. If the
bearing becomes rough or noisy, replace
it.
Generator
Troubleshooting
A complete and illustrated text on troubleshooting the
BID
series of generators
is
furnished in the
Technical Manual which
is
available through your local dealer.
WESTERBEKE GENERATORS
74