Service manual

BE
TROUBLESHOOTING
NOTE:
AC
GENERATOR
TROUBLESHOOTING
MUST
BE
PERFORMED
WITH ENGINE
OPERATING
AT
60 BER1Z.
FAULT
PROBABLE
CAUSE
No
AG
voltage
output
at
no
load.
Flesidual
voltage
produced
at
no
load
15
-
20
volts
AG.
Low
AG
voltage
output
at
no
load
60
-100
VAG.
High
AG
output
voltage
150
VAG
or
higher.
Unstable
voltage
output.
AG
voltage
drop
under
load
60
-100
volts
AG.
r------------,
EXCITER
STATOR
1.
Short
or
open
in
the
main
stator
winding.
2.
Shorted
pozi-resistor
on
exciter
rotor.
3.
Four
or
more
shorted
or
open
diodes
on
exciter
rotor.
1.
Blown
6
AMP
buse
fuse
auxiliary
circuit
feed
to
AVR.
2.
Faulty
voltage
regulator.
.
1.
Open
or
shorted
diodes
in
exciter
rotor
1
to
3
diodes.
2.
Open
or
shorted
exciter
rotor
winding.
1.
Faulty
voltage
regulator.
1.
STB
pod
on
regulator
needs
adjustment.
1.
Diode(s)
on
exciter
rotor
breaking
down
when
load
is
applied
(inductive)
1-3
diodes.
r----
-1--
------
---'
.
RED
. ,
,
:
EXCITER
RmRFlELD
....
---
---1
I I
,
STATOR.
J
4.
Short
or
open
in
exciter
stator
winding.
5.
Short
or
open
in
rotating
field
winding.
3.
Shorted
or
open
main
stator
auxiliary
winding.
3.
Faulty
voltage
regulator.
2.
Faulty
voltage
regulator.
RED
RED
~
__
~,
Rm~
~
!
......
I--,--~
J
RED
L_
§
....
>-
I J
AUX
J J
L
_____
~-~----_---~
_____
.J
---------~
.
REGULATOR
fUSE
RED
RED
BLUE
YEllOW
Engines & Generators
56
®
wz
BLACK
GREEN