Service manual

VOLTAGE
REGULATOR
ADJUSTMENTS
Description
The voltage regulator is an advanced design which ensures
optimum AC alternator performance.
It
is equipped with
complete protection circuitry to guard against operating
conditions that could be detrimental to the AC alternator.
This potentiometer is used to adjust output voltage. At proper
engine operating speed the output voltage should be held at
±1
% from a no-load condition to a full rated generator output
and from power factor
1.0 - 0.8 with engine drive speed vari-
ations
up
to
-6%.
Prior to starting the engine, turn the VOLT and STAB trim-
mers (using a mini phillips screwdriver) fully
ina
counter
clockwise (Minimum) direction until you feel them hit their
stops.
Tum the
AMP and HERTZ trimmers completely clockwise
(Maximum)
in
the same manner.
With the alternator running
at no-load, at normal speed, and
with
VOLT adjust at minimum, it is possible that output volt-
age will oscillate.
Slowly rotate the VOLT adjust clockwise.
The voltage output
of
the alternator will increase and stabi-
lize. Increase the voltage to the desired
~alue.
In
this situa-
tion, only the green LED will stay lit.
stability
This potentiometer permits variation
of
the regulator's
response to generator load changes so
as
to
limit overcom- .
pensation and obtain a minimum recovery time to the normal
voltage output.
In
order to adjust the regulator stability the alternator must be
running
a~
no-load and the output must
be
monitored.
Tum the STAB adjust slowly clockwise until the voltage
starts
to
fluctuate.
At
this point rotate the STAB adjust coun-
terclockwise until the voltage is stable within 1 or 2 tenths
of
a volt.
.!
green
'-
~
yeHow
L
Hertz
AmI!
Stab
Volt
VOLTAGE
REGULATOR
DIAGRAM
.
Amp-Hertz
These two adjustments are used
in
conjunction with the two
protection circuits in the voltage regulator that are indicated
by the illumination
of
a colored LED lights.
1. Delayed overload protection
(yellOW
LED).
2. Low speed protection (red LED).
Both systems have an intervention threshold which can
be
adjusted using the respective potentiometer. Each
of
the
two
circuits
are
able to cause an adequate reduction in excitor
voltage to safeguard the excitor windings and prevent their
overheating.
The
overload protection system has a delay which permits
temporary overloading
of
the generator during times
such
as
motor start-up
or
other similar load surge demands.
The
reg-
ulator also has a third LED (green), that
glows
during gener-
ator operation to indicate correct operation
of
the regulator
with the generator. . .
Setting
the
Overload
Protection
In
order to set the
AMP
overload protection, the alternator
must
be
loaded to its full output rating. .
1. Load the alternator
to
its rating, then decrease the speed
of
the engine by 10.10% (54 Hertz
on
60
hertz units, 45
hertz
on
50 hertz units).
2. Rotate the
AMP adjustment counterclockwise until it hits
its stop. Wait about 15-20 seconds after which the
AC
out-
put
of
the alternator should drop and the yellow LED light
should come on
..
3. Slowly rotate the
AMP
adjustment
cl~kwise
until the
output voltage increases to approximately
97%
of
the
voltage
output· at the start
of
the adjustment.
At
this point
the yellow LED light should come on.
4. Return
to
nominal speed, the yellow
LED
will turn
off
and the alternator voltage will.rise to its normal value.
Should this not happen, repeat the adjustment.
NOTE:
When changing from
60
hertz
to
50
hertz
operation,
remove
the
60
hertz jumper
bar
from the regulator board.
Setting
the
Underspeed.
Protection
NOTE:
If
the unit is operating
at
60
Hertz ensure that the
jumper strap
is
in place on the regulator board between the
two
60
Hertz terminals.
In
order to adjust the underspeed
setting, the alternator should
be
running
at
no-load.
1. To adjust the underspeed (low frequency) protection circuit,
lower the engine speed
at
90%
of
its normal running speed
(54 hertz on 60 hertz units, 45 hertz
on
50
hertz units.
2. Rotate the Hertz adjustment counterclockwise slowly until
the alternator's
AC
output voltage starts
to
decrease and at
the
same
time the red
"LED"
light
comes
on
.
3.
Increase the engine speed to its normal speed (frequency).
The
red "LED" light will
go
out and the
AC
voltage out-
put will return to normal.
With the above adjustments made, the regulator should func-
tion normally.
Engines & Generators
54