Installation manual
SAFETY
SHUTDOWN
SWITCHES
SAFETY
SHUTDOWN
SWITCHES
1i'he
engine
is
protected by three automatic shutdown
switches. Should a shutdown occur,
do
not
attempt to restart
without finding
and
correcting the cause. Refer to the head-
ing Engine starts, runs and then shuts down
in
the ENGINE
tROUBLESHOOTING section
of
this manual.
']'he following
is
a description
of
these automatic shutdown
switches:
High
Water
Temperature
Switch
A high water temperature switch is located at the thermostat
housing. Nonnally closed, this switch, should the fresh water
cbolant's operating temperature reach approximately
210
0
P
(99°C),
will open and inten'Upt the
DC
voltage thereby
shutting off the engine. This switch resets at
195"F (IOrC}.
WATER
tI'EMPERATURE
'SWITCH
\_->"'-
Low
Oil
Pressure
Switch
A low oil pressure shutdown switch is located off the
e;ngine's oil gallery. Normally open in a static state, this
switch's sensor monitors the engine's oil pressure. Should the
engine's oil pressure fall to 5-10 psi, this switch will open
interrupting the
DC
voltage thereby shutting off the engine.
OIL
PRESSURE
SWITCH
OIL
PRESSURE
SWITCH
WIRED
FOR
OPTIONAL
AUDIBLE
ALARM
High
Exhaust
Temperature
Switch
An
exhaust temperature switch is located on the exhaust
elbow. Nonnally closed,
tins switch will open and interrupt
the
DC
voltage (shutting off the engine) should the switch's
sensor indicate an excessive exhaust temperature (an inade-
quate supply
of
raw water causes high exhaust temperatures).
This switch opens
at
260-270oP (127-132°C). This switch
resets at approximately
225°P (107°C).
/
~'~-....."'.......-
/-:"............
EXHAUST
ELBOW
'/
.
EXHAUST
TEMPERATURE
SWITCH
Engine
Circuit
Breaker
The generator's engine is protected by an engine mounted
manual reset circuit breaker
(20 amps DC). Excessive current
draw or electrical overload anywhere in the
insllument panel
wiring or engine wiring will cause the breaker
to
trip. In this
event the generator will shut down because the opened
breaker interrupts the
DC
'circuit.
If
this should occur, check
and repair the source
of
the problem. After repairing the
fault, reset the breaker and restart the generator.
High
RPM
Shutdown
Switch
(Optional
Electronic
Governing)
An overspeed switch in the DC circuit shuts off the generators
engine when the engine's speed reaches 2175 rpm (approx.) by
opening the DC circuit to the K2 relay. After correcting the
problem, this switch can be re-set by momentarily depressing the
stop switch. refer to the
WIRING DIAGRAMS
in
this manual.
Engines & Generators
10