Operator`s manual
Starting 
Under 
Normal Conditions 
Follow the procedure below for normal starting 
of 
the generator. 
1. 
Make sure there is sufficient fuel on board.  Keep fuel tank(s) as full as possible.  Check the fuel filters 
and water separators for the presence 
of 
contaminants and/or water.  Drain and clean them as needed. 
2.  Check the coolant level in the plastic recovery tank.  Add coolant solution as needed. 
NOTE:  Excessive loss 
of 
coolant from the plastic recovery tank indicates a cooling system leak.  Check 
the entire cooling system 
and 
pressurize the system using a common automotive radiator pressure tester to 
locate  the leak.  In cases 
of 
excessive  coolant loss,  the system  must 
be 
refilled 
as 
outlined under the 
"PREPARATION FOR STARTING" section 
of 
this manual. 
3. 
Check the oil level 
in 
the engine sump 
and 
look for fuel leaks, particularly 
if 
signs 
of 
such leaks are 
found on the bottom 
of 
the engine 
or 
below the engine. 
Start the generator in accordance with the "STARTING PROCEDURE"  instructions in this manual and 
allow the engine's operating temperature 
to 
reach 140 - 150
0 
F before placing a load 
on 
it. 
Starting 
Under 
Cold Conditions 
Under extremely  cold temperatures, the  following  conditions  can occur.  Follow  the instructions  listed 
below when operating your engine 
in 
cold weather. 
Lubricating Oil Turns  Viscous - Make certain that the lubricating oil  used conforms with the ratings for 
the prevailing atmospheric temperature.  Refer to the "LUBRICATING 
SYSTEM" section 
ofthis 
manual 
for 
an 
atmospheric/oil viscosity specification table. 
Voltage Across the Battery Terminal Drops - Make certain that the battery  is  fully  charged to  ntinimize 
voltage drop across the battery terminals. 
The 
Temperature 
o/the 
Intake 
Air 
is 
Low 
and 
the Compression Temperature does not Rise 
Enough-
Allow  the glow  plugs  to  operate sufficiently to  aid  in starting during the preheat period whenever the 
temperature 
of 
the intake air is low and when the compression temperature does not rise enough.  Refer 
to 
the preheat chart found 
in 
the "STARTING PROCEDURE" section 
of 
this manual. 