Operator`s manual
Dry  stack-type  exhaust  systems 
(shown  to  the  right)  must be 
at-
tached 
to 
the  generator  engine's 
exhaust  manifold 
by 
means 
of 
a 
flexible  connector  pipe.  This 
system must be properly supported, 
insulated,  and routed 
so 
as not 
to 
allow water  to  enter  the  engine's 
cylinders 
by 
coming  in  through 
this  piping.  Provisions  must  be 
made 
for 
discharging  the  engine's 
raw cooling water overboard. 
Exbaust System Failures 
.-
.z. 
~I..."" 
.... 
~ 
... 
CD""'::'" 
~ 
j I 
._-, 
,  . 
~===14f.;;;1 
\r 
71'~.~. 
.. 
.., 
........ 
e:. 
': 
I: 
XM5UL 
Txo.1 
~ 
j. 
.. 
, 
51:_ 
•• 
TI:_ 
: 
.. 
T 
... 
::C: 
T"ftou,a.-
~" 
.. 
U,-I.. 
rXTTX 
.. 
c 
tf':l. 
... 
tt. 
" 
.... 
1 
DRY 
STACt 
EXHRUST 
When  the engine's 
raw 
water 
is 
fed 
into an exhaust 
system 
so 
that the 
full 
stream of this water strikes a 
surface,  erosion  takes  place.  This erosion 
may 
cause premature failures.  The proper design 
of 
either a 
water jacketed or water injected 
"wet" 
exhaust system 
to 
prevent this problem requires that the raw water 
inlet 
be 
positioned 
so 
that the entering stream 
of 
raw 
water does not directly strike a surface.  In addition, 
the velocity 
of 
the  entering 
raw 
water  stream  should be as 
low 
as  possible, which can 
be 
achieved 
by 
having inlet fittings as big in diameter as possible. 
The  best  protection  against carbon  monoxide poisoning  is a  daily  inspection 
of 
the complete  exhaust 
system.  Check for leaks around manifolds,  gaskets, and 
welds. 
Make sure exhaust lines are not beating 
surrounding  areas excessively. 
If 
excessive heat  is present, correct  the situation immediately. 
If 
you 
notice a change in the sound or  appearance  of the exhaust system, shut down  the unit  immediately and 
have the system inspected and repaired at once 
by 
a qualified mechanic. 
Make sure  there  are 
no 
unnecessary objects suspended  from  any portion  of the exhaust  lines.  Rigidly 
constructed exhaust  risers installed off the  exbaust  manifold  must not  exceed 8 Ibs in  total weight. 
Excessive  unsupported  weight could cause deflection  or  distortion 
of 
the  manifold  resulting  in damage 
and/or internal leaks.  Rigidly constructed riser assemblies that 
do 
exceed 8 
Ibs. 
must be  supported 
to 
the 
engine, not 
to 
the hull.  Inspect insulated portions of the exhaust system 
to 
ensure there is no deterioration 
of the insulation. 
II 
CAUTION 
II 
Prolonged  cranking intervals without tbe engine starting can  result  in filling  the 
engine-mounted exbaust system witb sea water coolant.  This may halJpen because 
tbe sea  water pump 
is 
pumping sea water tbrougb tbe  sea 
water 
cooling  system 
during cranking.  This  sea 
water 
can  enter tbe engine's cylinders by way  of tbe 
exbaust  manifold once tbe exhaust  system fills.  Prevent tbis from balJpening by 
closing tbe sea water supply througb-bull sbut-off,  drain tbe exbaust 
mumer, 
and 
correct tbe cause for the excessive engine cranking needed to obtain a start. Engine 
damage resulting from tbis type of sea water entry is  not a warrantable issue;  tbe 
owner/operator should keep tbis in mind. 
WESTERBEKE GENERATORS 
18 










