Installation manual
ENGINE
TROUBLESHOOTING
Problem
Possible
Cause
Starter
stays
energized
after
start.
1.Faulty
K1
relay.
2.Faulty
starter
solenoid.
Poor
performance
at
generator
speed.
1.
Low
octane
fuel.
2.Contaminated
fuel
pump.
Black
exhaust
smoke.
1.
Dirty
air
screen.
2.Generator
is
overfilled.
Blue
exhaust
smoke.
1.Lube
oil
is
diluted.
2.Crankcase
breather
tube
is
clogged.
3.High
lube
oil
level.
Check
engine
LED's
are
illuminated.
1.Diagnostic
software
required.
Speed
LED's
are
illuminated-no
flashing.
1.Throttle
shaft
sticking.
2.lntake
manifold
vacuum
leak.
Pair
of
Speed
LED
LED's
are
illuminated-flashing.
1.AC
generator
overload.
2.Fuel
starvation.
Exterior
alarm
LED
is
illuminated.
1.Loose
connection.
2.Faulty
fire
suppression
shutdown
devise.
Engines & Generators
29