Operator`s manual
General
Rating - Three
Phase
15KW - 60 Hertz
12KW - 50 Hertz
Voltage - 3
Phase (60 Hertz)
Voltage - 3 Phase (50 Hertz)
Amperage - 3 Phase (60 Hertz)
Amperage - 3 Phase (50 Hertz)
Generator Cooling
Air Requirements, (60 Hertz), at 1800 RPM
Brushless, six pole, revolving field.
Sealed lubricated single bearing
design. 12 Lead reconnectable for low voltage WYE, high voltage
Delta.
Solid State voltage regulator with protection circuitry.
Low
voltage WYE 208 volts
High voltage WYE 480 volts
DELTA
240 volts
High voltage WYE
380 volts
DELTA 220 volts
Low
voltage WYE 99 Amps
High voltage WYE 43 Amps
DELTA
86 Amps
High voltage WYE 43 Amps
DELTA
75 Amps
225 -
250
din
(6.37 - 7.08 cmm)
NOTE: Increase air supply 15% for 50 Hertz operation (1500 rpm)
Engine Combustion Air
Requirements,
(60 Hertz), at 1800 RPM
67
dm
(1.89 cmm)
TUNE-UP SPECIFICATIONS
Injector Pressure 1707 psi (120 kglcm
2
+ 10kglcm
2
- 0 kglcm
2
)
Engine Timing
19° BTDC ± .5°
GENERATOR
COMPARTMENT
Ambient Temperature
104° F(40°C) Maximum
NOTE: Forced ventilation should be provided as needed to maintain generator compartment ambient
temperature 104
0
F.
6