Installation manual

GENERATOR
INFORMATION
USE
OF
ELECTRIC
MOTORS
The power required to start an electric motor is considerably
more than is required to keep it running after it is started.
Some motors require much more current to start them than
others. Split-phase (AC) motors require more current to start,
under similar circumstances, than other types. They are com-
monly used
on
easy-starting loads, such as washing
machines,
or
where loads are applied after the motor is
started, such as small power tools. Because they require 5 to
7 times as much current to start as to run, their use should be
avoided, whenever possible,
if
the electric motor is to be dri-
ven by a small generator. Capacitor and repulsion-induction
motors require from 2 to 4 times as much current to start as
to run. The current required to start any motor varies with the
load connected to it.
An electric motor connected to an air
compressor, for example, will require more current than a
motor to which no load is connected.
In general, the current
required
to
start
115-
Volt
motors connected
to medium starting loads
will
be
approximately
as
follows:
MOTOR
SIZE
AMPS
FOR
AMPS
FOR
(HP)
RUNNING
STARTING
(AMPERES)
(AMPERES)
1/6
3.2
6.4
to
22.4*
1/4
4.6
9.2
to
32.2*
1/3
5.2
10.4
to
72.8*
1/2
7.2
14.4
to
29.2*
3/4
10.2
20.4
to
40.8*
1
13
26
to
52
*NOTE:
In the above table the
maximum
Amps for Starting is
more
for
some small motors than
for
larger ones. The reason
for
this is that the hardest starting types (split-phase) are not
made
in larger sizes.
Because. the heavy surge
of
current needed for starting
motors is required for only an instant, the generator will not
be
damaged
if
it can bring the motor up to speed in a few
seconds.
If
difficulty
is
experienced in starting motors, tum
off all other electrical loads and,
if
possible, reduce the load
on the electric motor.
Required
Operating
Speed
Run the generator first with no load applied, then at half the
generator's capacity, and finally loaded to its full capacity as
indicted on the generator's data plate. The output voltage
should be checked periodically to ensure proper operation
of
the generating plant and the appliances it supplies.
If
an AC
voltmeter or ampmeter is not installed to monitor voltage and
load, check it with a portable meter and amp probe.
NOTE:
When the vessel in which the generator is installed
contains
AC
equipment
of
120
volts only, it is recommended
that the generator's
AC
terminal
block
be
configured to pro-
vide one
120
volt
AC
hot leg
for
the vessel's distribution
panel. This will ensure
good
motor
starting response from the
generator.
Generator
Frequency
Adjustment
Frequency is a direct result
of
engine/generator speed, as indi-
cated by the following:
D When the generator is run at 1800 RPM, the AC voltage
output frequency is
60 Hertz.
Therefore, to change the generator's frequency, the generator's
drive engine's speed must be changed .along with a reconfig-
uring
of
the
AC
output connections at the generator.
Generator
Maintenance
D Maintaining reasonable cleanliness is important.
Connections
of
terminal boards and rectifiers may become
corroded, and insulation surfaces may start conducting
if
salts, dust, engine exhaust, carbon, etc. are allowed to
build up. Clogged ventilation openings may cause exces-
sive heating and reduced life
of
windings.
D For unusually severe conditions, thin rust-inhibiting
petroleum-base coatings, should be sprayed
or
brushed
over all surfaces to reduce rusting and corrosion.
D In addition to periodic cleaning, the generator should be
inspected for tightness
of
all connections, evidence
of
overheated terminals and loose
or
damaged wires.
D The drive discs on single bearing generators should be
checked periodically
if
possible for tightness
of
screws and
for any evidence
of
incipient cracking failure. Discs should
not be allowed to become rusty because rust
may
accelerate cracking. The bolts which fasten the drive disc
to the generator shaft must be hardened steel SAE grade 8,
identified by 6 radial marks, one at each
of
the 6 comers
of
the head.
D The rear armature bearing is lubricated and sealed; no
maintenance is required. However,
if
the bearing becomes
noisy
or
rough-sounding, have it replaced.
D Examine bearing at periodic intervals. No side movement
of
shaft should be detected when force is applied.
If
side
motion is detectable, inspect the bearing and shaft for
wear. Repair must be made quickly
or
major components
will rub and
~ause
n:ajor damage to generator.
41
CIRCUIT
BREAKER
A circuit breaker is installed on all WESTERBEKE
generators. This circuit breaker will automatically disconnect
generator power in case
cif
an electrical overload. The circuit
breaker can be manually shut off when servicing the
generator to ensure. that no power is corning into the boat.
Carbon
Monoxide
Detector
WESTERBEKE recommends mounting a carbon
monoxide detector in the vesssel's living quarters.
Carbon
Monoxide,
even
in
small
amounts,
is
deadly.
The presence
of
carbon monoxide indicates an exhaust leak
from the engine
or
generator
or
from the exhaust elbow/
exhaust hose,
or
that fumes from a nearby vessel are
entering your boat.