User Manual

8.3 Parameter level
µ Entrys marked with this symbol are selectable only with existing device-option.
Range rnG
Name Value range Description
rnG.L
-1999...9999
lower limit alarm for main alarm LC
rnG.H
-1999...9999
upper limit alarm for main alarm LC
Functions Func
Name Value range Description
tEmP
0...9999
probe temperature for O2- measurement µ
Inputs InP.1 and InP.2 µ
Name Value range Description
InL.1
(InL.2)
-1999...9999
Input value of the lower scaling point
Dependent on sensor type, the input values can be scaled to the display values at
parameter level. Specification of the input value of the lower scaling point is in
units of the relevant electrical quantity (mA/V/Ohm), e.g. 4 mA.
OuL.1
(OuL.2)
-1999...9999
Display value of the lower scaling point
Dependent on sensor type, the input values can be scaled to the display values at
parameter level. The operator can change the display value of the lower scaling
point, e.g. 4 mA is displayed as 2[pH].
InH.1
(InH.2)
-1999...9999
Input value of the upper scaling point
Dependent on sensor type, the input values can be scaled to the display values at
parameter level. Specification of the input value of the upper scaling point is in
units of the relevant electrical quantity (mA/V/Ohm), e.g. 20mA.
OuH.1
(OuH.2)
-1999...9999
Display value of the upper scaling point
Dependent on sensor type, the input values can be scaled to the display values at
parameter level. The operator can change the display value of the upper scaling
point, e.g. 20 mA is displayed as 12 [pH].
t.F1
(t.F2)
0...999,9
Filter time constant [s]
Each input is provided with a digital (software)low-pass filter for suppression of
process-dependent interference on the input leads. The higher the value, the bet-
ter the filter effect, but the longer the input signal delay.
E.tc1
(E.tc2)
OFF, 0...100
external cold junction compensation, range dependent of temperature unit
Limit values LC, Lim1 … Lim 3
Name Value range Description
LC
-1999...9999
Limit value LC. Limit value LC is the main function of the temperature monitor.
L.1
-1999...9999
Low limit value 1 (L.1< -1999 = off)
Alarm is active when exceeding and reset with low limit value plus hysteresis.
H.1
-1999...9999
High limit value 1 (H.1< -1999 = off)
Alarm is active when exceeding and reset with high limit value minus hysteresis.
HYS.1
0...9999
Hysteresis of limit value1/LC
Switching difference for high and low limit value. For limit alarm resetting, the value must
decrease by this value with high limit value and increase by this value with low limit value.
L.2
-1999...9999
lower limit 2 (L.2< -1999 = off) (s.u.)
H.2
-1999...9999
upper limit 2 (H.2< -1999 = off) (s.u.)
HYS.2
0...9999
Hysteresis of limit 2 (s.u.)
L.3
-1999...9999
lower limit 3 (L.3< -1999 = off) (s.u.)
H.3
-1999...9999
upper limit 3 (H.3< -1999 = off)(s.u.)
HYS.3
0...9999
Hysteresis of limit 3 (s.u.)
g
Resetting to factory setting (default)
r chapter 6.9 (page 32)
Parameter level
TB 45 Parameter level 41