Owner manual

4.2 Configuration
Lim
Name Value range Description Default
Fcn.1
Function of limit 1
3
3
Measured value monitoring + latching of the alarm status of
the upper limit. A latched alarm can be reset by the error
list, the digital input or the RESET-key (-> LOGI/
Err.r).
TW_S
1
4
Measured value monitoring + latching of the alarm status of
the lower limit. A latched alarm can be reset by the error
list, the digital input or the RESET-key (-> LOGI/
Err.r).
TW_S
1
5 Measured value monitoring upper limit (no latching)
TW
1
6 Measured value monitoring lower limit (no latching)
TW
1
Fcn.2 / 3
Function of limit2/3
0/0
0
switched off
1
measured value monitoring
2 Measured value monitoring + latching of the alarm status.
A latched alarm can be reset by the error list, the digital
input DI1 or the RESET-key (-> LOGI/ Err.r).
Src.2 / 3
Source of limit2/3
0/0
0
process value
1
control deviation xw (process value - set-point)
Hour
OFF...10000
Operating hours (only visible with BlueControl!)
OFF
Swit
OFF...10000
Output switching cycles (only visible with BlueControl!)
OFF
1 TW: Temperature monitor
TW_S: Temperature monitor with stored alarm
InP.1
Name Value range Description Default
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C), Fe-CuNi (DIN)
1
thermocouple type J (-100...1200°C), Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200...400°C), Cu-CuNi
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18
special thermocouple
Configuration level
Configuration 14 TB40-1