Instruction Manual

5 Parameter setting level
5.1 Parameter survey
PArA Parameter setting level
È
Ì
Lim
Limit value functions
InP.1
Input 1
rnG
LC setting range
End
LC InL.1 rnGL
L.2 OuL.1 rnGH
H.2 InH.1
HYS.2 OuH.1
L.3 tF.1
H.3
HYS.3
g
Adjustment:
w
The parameters can be adjusted by means of keys ÈÌ
w
Transition to the next parameter is by pressing key Ù
w
After the last parameter of a group, donE is displayed, followed by
automatic change to the next group.
+
Return to the beginning of a group is by pressing the Ù key for 3 sec.
5.2 Parameters
Lim
Name Value range Description Default
LC
-1999...9999
LC limit
100
L.2
-1999...9999
Lower limit 2
OFF
H.2
-1999...9999
Upper limit 2
OFF
HYS.2
0...9999
Hysteresis limit 2
1
L.3
-1999...9999
Lower limit 3
OFF
H.3
-1999...9999
Upper limit 3
OFF
HYS.3
0...9999
Hysteresis limit 3
1
L.3, H.3, Hys.3 only available if Fcn.1=TW
InP.1
Name Value range Description Default
InL.1
-1999...9999
Input value for the lower scaling point
0
OuL.1
-1999...9999
Displayed value for the lower scaling point
0
InH.1
-1999...9999
Input value for the upper scaling point
20
OuH.1
-1999...9999
Displayed value for the upper scaling point
20
t.F1
-1999...9999
Filter time constant [s]
0,5
Parameter setting level
Parameter survey 18 TB40-1