12 Technical data
INPUTS
SIGNAL INPUT INP
Accuracy: 0,01% at 25°C
Decimal point: 0 bis 3 decimals
Input filter: adjustable 0.0...999.9 s
Scanning cycle: 50 ms with 19 bit
Linearization: 31 Segments, adaptable with
BlueControl
®
Calibration: with/without shunt calibration
Measurement value cor
-
rection:
2-point
Limiting frequency 1.7Hz
Measurement value cor
-
rection:
Sensor break, short circuit and po
-
larity
Connection technology: 4-wire bridge
6-wire bridge (Sense line)
Input range
Span start, span end any, within measuring range
Scaling any, -1999 ...9999
Measurement span:
with Us = 10V
Slope/ sensitivity 0.5 mV/V 5 mV
1 mV/V 10 mV
2 mV/V 20 mV
4 mV/V 40 mV
DIGITALINPUT DI1
Operation as
Contact input
Connection of a potential-free contact that is suitable for
switching ‘dry’ circuits.
Switched voltage: 5V
Current: 0.5 mA
Function
Configurable as direct or inverse switch or push button!
Functions: Operation disabling, reset of stored alarms and the
min/max indicator (slave pointer), the integrator,
enabling the tare function,Sample&Hold amplifier
function, Cal-Test , and zero setting.
OUTPUTS
RELAY OUTPUTS OUT1, OUT2
Contact type: 2 normally open with common
contact connection
Max. contact rating: 500 VA, max. 250 V, max. 2A
at 48...62 Hz, ohmic load
Min. contact rating: 6V, 1 mA DC
Swithing cycles (electrical): for I=1A/2A: ?
800,000/500,000 (at~250V
(ohmic load))
Note:
If the relays OUT1, 2 and 3 are used to operate external contac
-
tors, these must be fitted with RC snubber circuits to manufactu
-
rer specifications to prevent excessive voltage peaks at
switch-off.
OUT3 AS UNIVERSAL OUTPUT
Parallel current/voltage output with common ‘minus’ terminal
(combined use only in galvanically isolated circuits).
Freely scalable
Resolution: 14 Bit
Dynamic response
(step change of input signal) T
90
:
Output follows the in-
put within 300 ms
Tracking error I/U:
Residual ripple:
(rel. to range end)
£ 2%
ß_1%
0...130 kHz
Current output
0/4...20 mA, configurable, short-circuit proof.
Control range: -0.5....23 mA
Load: £ 600 [
Load effect: ß0.02%
Resolution: ß 1.5 úA
Error: ß 0.1%
Voltage output
0/2...10V, configurable, not permanently short-circuit proof
Control range: 0.15...11.5 V
Load: ? 2k[
Load effect: ß0.06%
Resolution: ß 0.75 mV
Error:
Additional error when using simultaneous
-
ly the current output
ß 0.1%
ß+0.09%
Output values can be preset via interface (Forcing)
Technical data