User Manual
ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008 Modbus Parameters Page 89
Option Slot 2 Parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Module Fitted In Slot 2
0 None Fitted
1 Single Relay
2 Single SSR Driver
3 Linear mA/V DC
8 Triac
9 Dual Relay
10 Dual SSR Driver
11 24VDC Transmitter PSU
Option Slot 2
Module Type
2160 0x0870 RO
255
Error (unrecognised module)
Value Linear Output 2 Type
0 0 to 5V DC
1 0 to 10V DC
2 2 to 10V DC
3 0 to 20mA DC
4 4 to 20mA DC
Linear mA/V DC
Output 2 Type
2161 0x0871 R/W
5 Variable 0 to 10VDC Transmitter PSU
Value Digital Output 2 or 2A Status
0 Inactive
Digital Output 2 or
2A Status
2162 0x0872 RO
1 Active
Value Digital Output 2B Status
0 Inactive
Digital Output 2B
Status
2163 0x0873 RO
1 Active
Linear Output 2
Level Status
2164 0x0874 RO -2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value Linear Output 2 or 2A Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Retransmit Actual Setpoint Value
Linear Output 2 or
2A Function
2174 0x087E R/W
4 Retransmit Process Variable Value
Value Digital Output 2 or 2A Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
Digital Output 2 or
2A Function
2176 0x0880 R/W
4 Alarm and Event