59407, Issue 1 March 2008 Modbus Parameters Page 87
Option Slot 1 Parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Module Fitted In Slot 1
0 None Fitted
1 Single Relay
2 Single SSR Driver
3 Linear mA/V DC
8 Triac
Option Slot 1
Module Type
2130 0x0852 RO
255
Error (unrecognised module)
Value Linear Output 1 Type
0 0 to 5V DC
1 0 to 10V DC
2 2 to 10V DC
3 0 to 20mA DC
4 4 to 20mA DC
Linear mA/V DC
Output 1 Type
2131 0x0853 R/W
5 Variable 0 to 10VDC Transmitter PSU
Value Digital Output 1 Status
0 Inactive
Digital Output 1
Status
2132 0x0854 RO
1 Active
Linear Output 1
Level Status
2134 0x0856 RO -2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value Linear Output 1 Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Retransmit Actual Setpoint Value
Linear Output 1
Function
2144 0x0860 R/W
4 Retransmit Process Variable Value
Value Digital Output 1 Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
Digital Output 1
Function
2146 0x0862 R/W
4 Alarm and Event
Value Output 1 Alarm Selection
0 Alarm 1. Direct Acting
1 Alarm 1. Reverse Acting
2 Alarm 2, Direct Acting
3 Alarm 2. Reverse Acting
4 Alarm 3. Direct Acting
5 Alarm 3. Reverse Acting
6 Alarm 4. Direct Acting
7 Alarm 4. Reverse Acting
8 Alarm 5. Direct Acting
9 Alarm 5. Reverse Acting
10 OR of Alarm 1 or 2. Direct
Output 1 Alarm
Selection
2148 0x0864 R/W
11 OR of Alarm 1 or 2. Reverse