59407, Issue 1 – March 2008 Modbus Parameters Page 85
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Scale Point 14 1080 0x0438 R/W >Scale point 13 to 100.0%
Display Point 14 1081 0x0439 R/W Valid between scale range maximum and minimum
Scale Point 15 1082 0x043A R/W >Scale point 14 to 100.0%
Display Point 15 1083 0x043B R/W Valid between scale range maximum and minimum
Option Slot A Parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Digital Input A Status
0 Inactive
Digital Input A Status 2115 0x0845 RO
1 Active
Value Module Fitted In Slot A
0 None Fitted
1 RS485 Communications
3 Digital Input
4 Auxiliary Input A
5 Ethernet Communications
Option Slot A
Module Type
2116 0x0844 RO
255
Error (unrecognised module)
Value RS485 Address
0 Modbus Master mode
RS485 Address 2117 0x0845 R/W
1 to 255 Modbus Slave Address
Value Baud Rate
0 4800
1 9600
2
19200 (Default)
3 38400
4 57600
RS485 Data Rate 2118 0x0846 R/W
5 115200
Value Parity
0 None
1 Even
RS485 Parity 2119 0x0847 R/W
2 Odd
Value Auxiliary A Input Type
0 0 to 20mA DC
1 4 to 20mA DC
2 0 to 10V DC
3 2 to 10V DC
4 0 to 5V DC
Auxiliary Input A
Type
2120 0x0848 R/W
5 1 to 5V DC
Target Setpoint
Address
2121 0x0849 R/W Target setpoint parameter address for master mode
Value Data Format
0 Integer
1 Integer with 1 decimal place
Master Transmit
Format
2123 0x084B R/W
2 Floating point number