User Manual

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 128 Modbus Parameters 59407, Issue 1 March 2008
Instrument Data
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Serial Number 1 210 0x00D2 RO The first 4 digits of the instrument’s Serial number.
Serial Number 2 211 0x00D3 RO The digits 5 to 8 of the instrument’s Serial number.
Serial Number 3 212 0x00D4 RO The digits 9 to 11 of the instrument’s Serial number.
Serial Number 4 213 0x00D5 RO The digits 12 to 14 of the instrument’s Serial number.
Manufacture Day 370 0x0172 RO Date of manufacture 1 to 31 (day of month)
Manufacture Month 371 0x0173 RO Month of manufacture 1 to 12
Manufacture Year 372 0x0174 RO 4 digit number = Year of manufacture (e.g. 2008)
Value USB Option
0 Not Fitted
USB Option Fitted 7503 0x1D4F RO
1 Fitted
Value Data Recorder Fitted
0 Not Fitted
Data Recorder
Fitted
7868 0x1EBC RO
1 Fitted
Value Profiler Enabled
0 Profiler Not Enabled
Profiler Enabled 8199 0x2007 RO
1 Profiler Enabled
Software PRL 208 0x00D0 RO Product Revision Level Firmware Level
Hardware PRL 207 0x00CF RO Product Revision Level Hardware Level
Firmware Type 217 0x00D9 RO Firmware major version number
Firmware Version 218 0x00DA RO Firmware minor version number
Contact Details 1 400 0x0190 R/W
Contact Details 2 401 0x0191 R/W
Contact Details 3 402 0x0192 R/W
Contact Details 4 403 0x0193 R/W
Contact Details 5 404 0x0194 R/W
Contact Details 6 405 0x0195 R/W
Contact Details 7 406 0x0196 R/W
7 lines of user definable text - 26 ASCII characters
per line which can re read or written using Modbus
functions 16 or 23. Valid characters are 0 to 9, a to z,
A to Z, plus ( ) - and _.
Example. To write “My Company Name” to line 1
send:
[ADDRESS], 16, 01, 90, 00, 08, 10, 4D, 79, 20, 43,
6F, 6D, 70, 61, 6E, 79, 20, 4E, 61, 6D, 65, [CRC]