59407, Issue 1 – March 2008 Modbus Parameters Page 111
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Trend View Data
0 None (trend view off)
1 Process variable only
2 Process variable and setpoint
Values To Display In
Trend View
9001 0x2329 R/W
3 Process variable maximum & minimum
since last sample
Profiler Control & Status Parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Profile Run/Hold Signal Source
0 Operator Key Press Only
1 Digital input A
Profile Run/Hold
Signal
8192 0x2000 R/W
2 Digital input B
Value Profile Abort Signal Source
0 Operator Key Press Only
1 Digital input A
Profile Abort Signal 8193 0x2001 R/W
2 Digital input B
Active Profiler
Number
8243 0x2033 R/W Currently selected profile number (1 to 64)
Active Segment
Number
8244 0x2034 RO Currently active segment (1 to 255)
Value Profiler Command
0 Do nothing
1 Run the currently selected profile
2 Hold the currently running profile
3 Abort the currently running profile
4 Jump to the next segment
5 Release the hold
Profiler Control
Commands
8245 0x2035 R/W
6 Exit profiler, return to controller mode
Note: The Profiler Control Commands must be followed by a Profiler Control Confirmation Action command.
Value Implement Profiler Command
0 Do Not Implement Command
Profiler Control
Confirmation Action
8257 0x2041 R/W
1 Implement previous Profiler Command
Value Editing Current Running Profile
0 Editing current running profile forbidden
Enable Edit While
Running
8262 0x2046 R/W
1 Editing current running profile allowed
Value Profile Control From Operation Mode
0 Operation Mode profile control disabled
Profile Control In
Operation Mode
8260 0x2044 R/W
1 Operation Mode profile control enabled
Profile Cycles Run 8247 0x2037 RO The Number of times the currently running profile has
cycled
Value Status Of Event 1
0 Event 1 Inactive
Event 1 Status 8249 0x2039 RO
1 Event 1 Active