User Manual
ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 110 Modbus Parameters 59407, Issue 1 – March 2008
Parameter Name Modbus Address Access Values
(Dec) (Hex)
16 Profile Running
17 Profile Ended
Value Backlight Colour
0 Green to Red on Alarm
1 Red to Green on Alarm
2 Permanent Green
Backlight Colour 7668 0x1DF4 R/W
3 Permanent Red
Value Language
0 Main Display Language
Display Language 7675 0x1DFB R/W
1 Alternate Display Language
Display Contrast 7676 0x1DFC R/W 0 to 127
Value Invert Display
0 Normal Display
Invert Display 7677 0x1DFD R/W
1 Inverted Display
Setup Lock Code 7678 0x1DFE R/W 1 to 9999. Default is 10
Configuration Lock
Code
7679 0x1DFF R/W 1 to 9999. Default is 10
Tuning Lock Code 7680 0x1E00 R/W 1 to 9999. Default is 10
Supervisor Lock
Code
7681 0x1E01 R/W 1 to 9999. Default is 10
Profiler Lock Code 7682 0x1E02 R/W 1 to 9999. Default is 10
USB Lock Code 7683 0x1E03 R/W 1 to 9999. Default is 10
Recorder Lock Code 7684 0x1E04 R/W 1 to 9999. Default is 10
Value Read Only Operation Mode
0 Operation Mode Read/Write
Read Only
Operation Mode
7685 0x1E05 R/W
1 Operation Mode Read Only
Value Bar Graph Format
0 Power Output
1 Control Deviation
Bar Graph Format 7686 0x1E06 R/W
2 % Memory Remaining
Value Trend Sample Interval
0 Every Second
1 Every 2 Seconds
2 Every 5 Seconds
3 Every 10 Seconds
4 Every 15 Seconds
5 Every 30 Seconds
6 Every Minute
7 Every 2 Minutes
8 Every 5 Minutes
9 Every 10 Minutes
10 Every 15 Minutes
Trend View Sample
Interval
9000 0x2328 R/W
11 Every 30 Minutes