59407, Issue 1 March 2008 Modbus Parameters Page 107
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Record Power Turned On/Off
0 Do Not Record Power On/Off
Record Power 7583 0x1D9F R/W
1 Record Power On/Off
Value Alarm 1 To Trigger Recording
0 Off
Trigger Recording
On Alarm 1
7584 0x1DA0 R/W
1
Trigger On Alarm 1 (if trigger is alarm)
Value Alarm 2 To Trigger Recording
0 Off
Trigger Recording
On Alarm 2
7685 0x1DA1 R/W
1
Trigger On Alarm 2 (if trigger is alarm)
Value Alarm 3 To Trigger Recording
0 Off
Trigger Recording
On Alarm 3
7686 0x1DA2 R/W
1
Trigger On Alarm 3 (if trigger is alarm)
Value Alarm 4 To Trigger Recording
0 Off
Trigger Recording
On Alarm 4
7687 0x1DA3 R/W
1
Trigger On Alarm 4 (if trigger is alarm)
Value Alarm 5 To Trigger Recording
0 Off
Trigger Recording
On Alarm 5
7688 0x1DA4 R/W
1
Trigger On Alarm 5 (if trigger is alarm)
Sample Size 7595 0x1DA5 RO Size in bytes, for current setup of recording sample
Value Record Change Of State For Event 1
0 Do Not Record Event 1
Record Event 1 7599 0x1DAF R/W
1 Record Event 1
Value Record Change Of State For Event 2
0 Do Not Record Event 2
Record Event 2 7600 0x1DB0 R/W
1 Record Event 2
Value Record Change Of State For Event 3
0 Do Not Record Event 3
Record Event 3 7601 0x1DB1 R/W
1 Record Event 3
Value Record Change Of State For Event 4
0 Do Not Record Event 4
Record Event 4 7602 0x1DB2 R/W
1 Record Event 4
Value Record Change Of State For Event 5
0 Do Not Record Event 5
Record Event 5 7603 0x1DB3 R/W
1 Record Event 5
Memory Used 7605 0x1DB5 RO
Recorder Memory Used. 0 (Empty) to 100% (Full)
Value Display Date Format
0 dd/mm/yyyy (European Default)
Date format 7868 0x1EBC R/W
1 mm/dd/yyyy (USA Default)
Time 7869 0x1EBD R/W Format is the number of seconds since midnight.
Date 7870 0x1EBE R/W Format 6 digits. Example 280308 for 28/03/2008
Value Real Time Clock Fitted
0 Not Fitted
Real Time Clock
Fitted
7871 0x1EBF RO
1 Fitted