User Manual

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 March 2008 Modbus Parameters Page 105
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Alarm 5 Type
0 Process High Alarm
1 Process Low Alarm
2 Deviation Alarm (SP-PV)
3 Band Alarm
4 Loop Alarm
5 Input/Sensor Break Alarm
6 Auxiliary Input A Break Alarm
Alarm 5 Type 6208 0x1840 R/W
7 Auxiliary Input B Break Alarm
Alarm 5 Value 6209 0x1841 R/W Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis 6210 0x1842 R/W Limited by the input span
Value Alarm 5 Inhibit Enable
0 Disabled
Alarm 5 Inhibit
Enable/disable
6211 0x1843 R/W
1 Enabled
Value Alarm 5 Status
0 Inactive
Alarm 5 Status 6212 0x1844 RO
1 Active
Value Alarm 5 Inhibit Status
0 Not Inhibited
Alarm 5 Inhibit
Status
6213 0x1845 RO
1 Inhibited
Recorder & Clock Parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value
0 Every Second
1 Every 2 Seconds
2 Every 5 Seconds
3 Every 10 Seconds
4 Every 15 Seconds
5 Every 30 Seconds
6 Every Minute
7 Every 2 Minutes
8 Every 5 Minutes
9 Every 10 Minutes
10 Every 15 Minutes
Recording Sample
Interval
7550 0x1D7E R/W
11 Every 30 Minutes
Value Recording Mode
0 Record until memory used
Recording Mode 7551 0x1D7F R/W
1 Continuous FIFO buffer
Value Operator Start/Stop Recording
0 Stop Recording
Start Stop
Recording
7552 0x1D80 R/W
1 Start Recording