ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 1 – March 2008 Modbus Parameters Page 103
Alarm parameters
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Value Alarm 1 Type
0 Process High Alarm
1 Process Low Alarm
2 Deviation Alarm (SP-PV)
3 Band Alarm
4 Loop Alarm
5 Input/Sensor Break Alarm
6 Auxiliary Input A Break Alarm
Alarm 1 Type 6144 0x1800 R/W
7 Auxiliary Input B Break Alarm
Alarm 1 Value 6145 0x1801 R/W Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 1 Hysteresis 6146 0x1802 R/W Limited by the input span
Value Alarm 1 Inhibit Enable
0 Disabled
Alarm 1 Inhibit
Enable/disable
6147 0x1803 R/W
1 Enabled
Value Alarm 1 Status
0 Inactive
Alarm 1 Status 6148 0x1804 RO
1 Active
Value Alarm 1 Inhibit Status
0 Not Inhibited
Alarm 1 Inhibit
Status
6149 0x1805 RO
1 Inhibited
Value Alarm 2 Type
0 Process High Alarm
1 Process Low Alarm
2 Deviation Alarm (SP-PV)
3 Band Alarm
4 Loop Alarm
5 Input/Sensor Break Alarm
6 Auxiliary Input A Break Alarm
Alarm 2 Type 6160 0x1810 R/W
7 Auxiliary Input B Break Alarm
Alarm 2 Value 6161 0x1811 R/W Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 2 Hysteresis 6162 0x1812 R/W Limited by the input span
Value Alarm 2 Inhibit Enable
0 Disabled
Alarm 2 Inhibit
Enable/disable
6163 0x1813 R/W
1 Enabled
Value Alarm 2 Status
0 Inactive
Alarm 2 Status 6164 0x1814 RO
1 Active
Value Alarm 2 Inhibit Status
0 Not Inhibited
Alarm 2 Inhibit
Status
6165 0x1815 RO
1 Inhibited