Owner's manual

Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013 Page 112
Function 08 - Loopback Diagnostic Test
QUERY: Function 08 - Loopback Diagnostic Test
Func
Code
Diagnostic
Code
Value
08
00
00
HI
LO
RESPONSE: Function 08 - Loopback Diagnostic Test
Func
Code
Sub-function
Value
08
00
00
HI
LO
Note: The Response normally returns the same data as the loopback query.
Other diagnostic codes are not supported.
Function 16 - Write Multiple Registers (0x10 Hex)
Writes consecutive word (two-byte) values starting at the specified address.
QUERY: Function 16 - Write Multiple Registers (0x10 Hex)
Func
Code
1
st
Write
Address
Number of
Words
Byte
Count
1st Word
etc
Last Word
10
HI
LO
HI
LO
xx
HI
LO
HI
LO
RESPONSE: Function 16 - Write Multiple Registers (0x10 Hex)
Func
Code
1st Word
Address
Number of
Words
10
HI
LO
HI
LO
Note: The maximum number of data bytes that can be written in one message is
253 bytes.
Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Reads and writes the requested number of consecutive words (two-bytes) starting at the
specified addresses.
QUERY: Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Func
Code
1
st
Read
Address
Number of
Words
1
st
Write
Address
Number of
Write Words
Byte
Count
Values to Write
1st Word
etc
Last Word
17
HI
LO
HI
LO
HI
LO
HI
LO
xx
HI
LO
HI
LO
RESPONSE: Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Func
Code
Byte
Count
Read Data
1st Word
etc
Last Word
17
xx
HI
LO
HI
LO
Note: The maximum number of data bytes that can be read and written in one
message is 253 bytes.
Exception Responses
If a QUERY is sent without a communication error, but the instrument cannot interpret it, an
Exception RESPONSE is returned. The exception response consists of a modified version of
the original function code and an exception code that explains what was wrong with the
message. Possible exception responses and their reasons are: